# Hydraulic Magnetic Circuit Breaker – Construction, Working and Application

- Link: https://studyelectrical.com/2024/03/hydraulic-magnetic-circuit-breaker.html
- Published: 2024-03-21T14:44:38+00:00
- Author: Tesla

The** hydraulic magnetic circuit breaker** is a specialized electrical [switchgear](https://studyelectrical.com/2015/07/what-is-switchgear-features-components-hv-mv-lv.html)
device that integrates overload and fault protection within a single mechanism, 
eliminating the need for separate thermal and magnetic mechanisms.

It is particularly useful in environments where traditional thermal protection circuit
breaker may fail due to extreme temperatures or moisture conditions. Low temperatures
might prevent thermal protection from tripping, while high temperatures might make
it trip accidentally.

To overcome these limitations, an alternative solution like the **hydraulic magnetic
circuit breaker** becomes essential.

#### Key Features:

 * **Operational Range:** Available for a wide range of operational voltages up 
   to 240 volts and frequencies of both 50 Hz and 60 Hz.
 * **Variety:** Offered in one, two, and three-pole versions to suit various circuit
   configurations.
 * **Current Ratings:** Typically below 100 amperes, comparable to [miniature circuit breakers](https://studyelectrical.com/2014/07/miniature-circuit-breakers-mcb-types-characteristic-curves.html).

## Construction

The construction and different parts of **hydraulic magnetic circuit breaker** is
given below.

![Hydraulic Magnetic Circuit breaker Construction](https://studyelectrical.com/wp-
content/uploads/2024/03/Hydraulic-Magnetic-Circuit-breaker.webp)

1. Handle
2. Mechanism assembly3. Line terminal4. Fixed contact5. Contact tips6.
Moving contact7. Arc runner line side8. Hermetically sealed tube9. Magnetic frame10.
Solenoid coil11. Armature12. Load terminal13. Pole piece14. Arc runner load side15.
Arc grids16. Clip-in springs

The construction of a Hydraulic Magnetic Circuit Breaker involves several key components:

 1.  **Handle**: Provides manual operation for switching the circuit breaker on or 
     off.
 2.  **Mechanism Assembly**: Contains the internal mechanism responsible for tripping
     the breaker in case of overload or fault.
 3.  **Line Terminal**: Connects the circuit breaker to the incoming power supply line.
 4.  **Fixed Contact**: Stationary contact point within the breaker for conducting 
     electrical current.
 5.  **Contact Tips**: Points of electrical contact between the moving and fixed contacts,
     ensuring current flow.
 6.  **Moving Contact**: Mobile contact point that engages and disengages with the 
     fixed contact during operation.
 7.  **Arc Runner Line Side**: Component designed to guide and manage electrical arcs
     generated during circuit interruption on the line side of the breaker.
 8.  **Hermetically Sealed Tube**: Enclosure containing the damping fluid, ensuring
     consistent performance across various temperatures.
 9.  **Magnetic Frame**: Provides structural support and alignment for the solenoid
     coil and armature.
 10. **Solenoid Coil**: Generates a magnetic field when current passes through, contributing
     to the operation of the breaker mechanism.
 11. **Armature**: Movable component within the solenoid coil assembly, influenced 
     by magnetic forces to trip the breaker.
 12. **Load Terminal**: Connects the circuit breaker to the outgoing load circuit.
 13. **Pole Piece**: Component that directs and concentrates the magnetic flux generated
     by the solenoid coil.
 14. **Arc Runner Load Side**: Component similar to the arc runner line side, but located
     on the load side of the breaker.
 15. **Arc Grids**: Grid-like structures positioned to control and extinguish electrical
     arcs produced during circuit interruption.
 16. **Clip-in Springs**: Springs used for securing and positioning various components
     within the breaker assembly.

These components work together to provide reliable overload and fault protection
in hydraulic magnetic circuit breakers, ensuring safe and efficient operation of
electrical systems.

## Working Principle

Hydraulic magnetic circuit breakers provide both overload and fault protection with
a single mechanism:

 * a **solenoid coil** is combined with
 * a **spring-loaded actuator inside a cylinder** filled with a **dampening fluid**,

Hence the name of **hydraulic magnetic circuit breaker.**

![Solenoid and Spring loaded actuator inside cylinder filled with dampening fluid(
1)](https://studyelectrical.com/wp-content/uploads/2024/03/Solenoid-and-Spring-loaded-
actuator-inside-cylinder-filled-with-dampening-fluid-1.webp)

Solenoid and Spring loaded actuator inside cylinder filled with dampening fluid

### Hydraulic-Magnetic Technology

Hydraulic-magnetic circuit breakers operate based on the magnetic force generated
by the flow of load current through a solenoid coil connected in series. Here’s 
how they function:

Normal Operation:

![Rated Current or Less](https://studyelectrical.com/wp-content/uploads/2024/03/
Rated-Current-or-Less.webp)

Rated Current or Less

 * At or below the circuit breaker’s rated current, the magnetic flux in the solenoid
   is insufficient to attract the core towards the pole piece due to the opposing
   force of the spring.
 * Consequently, the [circuit breaker](https://studyelectrical.com/2018/12/circuit-breaker-operating-principle-and.html)
   remains closed, and the circuit remains energized.

**Overload**:

![Overload Current (Time Delay)](https://studyelectrical.com/wp-content/uploads/
2024/03/Overload-Current-Time-Delay.webp)

Overload Current (Time Delay)

 * When an overload occurs, where the current exceeds the breaker’s rating, the 
   magnetic flux in the solenoid starts pulling the core towards the pole piece.
 * The movement of the core is regulated by the hydraulic fluid, creating a controlled
   time delay proportional to the overload magnitude. This delay allows for temporary
   overloads, like motor startups, to pass without tripping the breaker.
 * If the overload persists, the core eventually reaches the pole piece, reducing
   the reluctance of the magnetic circuit.
 * As a result, the armature is attracted to the pole piece with enough force to
   collapse the latch mechanism, tripping the breaker.
 * The contacts separate, interrupting the current flow, and the core returns to
   its rest position.

![Overload Current (Trip)](https://studyelectrical.com/wp-content/uploads/2024/03/
Overload-Current-Trip.webp)

Overload Current (Trip)

**Short Circuit:**

 * In cases of high overloads or short circuits, the magnetic flux from the coil
   can instantly attract the armature to the pole face, even before the core moves.
 * This instantaneous trip feature is present in the breaker’s characteristic curve.
 * Unlike thermal circuit breakers, the trip point of hydraulic-magnetic breakers
   remains unaffected by ambient temperature.
 * After tripping, the breaker can be immediately re-closed without requiring a 
   cooldown period.

![Instantaneous Trip](https://studyelectrical.com/wp-content/uploads/2024/03/Instantaneous-
Trip.webp)

Instantaneous Trip

**Customization:**

 * Due to the operating principle, hydraulic-magnetic circuit breakers can be designed
   with various time-current characteristics to suit specific applications.

Hydraulic-magnetic circuit breakers offer reliable protection against overload and
[short circuit](https://studyelectrical.com/2016/03/short-circuit-causes-and-effects-application.html)
conditions, with the added benefit of consistent performance across a range of temperatures.

## Hydraulic Magnetic Circuit Breaker vs Thermal Magnetic Circuit Breaker

Here’s a breakdown of the main differences between hydraulic-magnetic circuit breakers
and thermal-magnetic circuit breakers:

 1. **Overload Protection Mechanism:**
 2.  * _Thermal-Magnetic Circuit Breakers_: Use a [bimetallic strip](https://www.fictiv.com/articles/the-bimetallic-strip-explained)
       that expands and contracts in response to temperature changes caused by overload
       currents. The strip interrupts the circuit when it expands sufficiently.
     * _Hydraulic-Magnetic Circuit Breakers_: Employ a solenoid coil and a dampened
       spring actuator to provide time-delayed disconnection in case of overload. The
       solenoid coil generates a magnetic field that attracts a core towards a pole
       piece, causing the mechanism to trip after a controlled time delay.
 3. **Fault Protection Mechanism:**
 4.  * _Both Types_: Share the same working principle for fault protection. During 
       a fault like a short circuit or line-to-ground fault, very high currents induce
       a strong magnetic field in the solenoid coil. This magnetic field causes the
       contacts to open, interrupting the circuit.
     * _Hydraulic-Magnetic Breakers_: The damping cylinder does not cause a time delay
       in this scenario, as the current and induced magnetic field are extremely strong,
       leading to an instantaneous trip.
 5. **Function and Application:**
 6.  * _Both Types_: Serve the same purpose of providing overload and fault protection
       in electrical circuits.
     * _Thermal-Magnetic Breakers_: Suitable for use in applications where temperature
       variations are not a concern.
     * _Hydraulic-Magnetic Breakers_: Preferred in environments where temperature extremes
       might affect the performance of thermal protection mechanisms.
 7. **Specialized Characteristics:**
 8.  * Each type of breaker has specialized characteristics that make it suitable for
       specific applications.
     * _Thermal-magnetic breakers_ are commonly used in standard electrical installations
       where temperature is not expected to vary significantly.
     * _Hydraulic-magnetic breakers_ are recommended for environments with extreme 
       temperatures or where consistent performance across a wide temperature range
       is required.

Hydraulic magnetic circuit breaker working

| Feature | Thermal-Magnetic Circuit Breakers | Hydraulic-Magnetic Circuit Breakers | 
| Overload Protection Mechanism | Bimetallic strip expands and contracts with temperature changes caused by overload currents, interrupting the circuit when sufficiently expanded. | Solenoid coil and dampened spring actuator provide time-delayed disconnection in case of overload. The solenoid coil generates a magnetic field that attracts a core towards a pole piece, causing the mechanism to trip after a controlled time delay. | 
| Fault Protection Mechanism | Very high currents induce a strong magnetic field in the solenoid coil, causing the contacts to open and interrupting the circuit. | Similar to thermal-magnetic breakers, very high currents induce a strong magnetic field in the solenoid coil, causing the contacts to open and interrupting the circuit. The damping cylinder does not cause a time delay in this scenario, leading to an instantaneous trip. | 
| Function and Application | Provides overload and fault protection in electrical circuits. | Serves the same purpose of providing overload and fault protection in electrical circuits. | 
| Suitability for Temperature Variations | Suitable for use in applications where temperature variations are not a concern. | Preferred in environments where temperature extremes might affect the performance of thermal protection mechanisms. | 
| Specialized Characteristics | Relies on temperature-sensitive bimetallic strips for overload protection. | Uses solenoid coils and dampened spring actuators for overload protection, making them more suitable for applications where temperature variations might affect performance. |

## Applications

Application of hydraulic magnetic circuit breakers are given below.

 * **Marine Environments:** Ideal for boats due to their resistance to moisture 
   and temperature extremes.
 * **Land Transportation:** Used in vehicles subject to heat and external temperature
   fluctuations.
 * **Electric Generator Rooms:** Ensures backup power is not accidentally interrupted
   due to thermal protection failure.
 * **Outdoor Locations:** Suitable for electric distribution boxes in harsh climates.
 * **Industrial Settings:** Provides reliable protection in environments with high
   temperatures.
 * **Sensitive Equipment:** Used where precise current sensing is required, and 
   thermal protection may not be adequate.

## Summary

In summary, hydraulic magnetic circuit breakers offer robust protection against 
overloads and faults in environments where traditional thermal protection may be
unreliable. Their versatility and reliability make them suitable for a wide range
of applications, particularly those with challenging environmental conditions.

### Related posts:

 [ ⌊HRC Fuse⌉Low Voltage Fuses: Types and Examples](https://studyelectrical.com/2023/09/low-voltage-fuses.html)
[ ⌊Generator Reactors⌉Current Limiting Reactor or Series Reactor](https://studyelectrical.com/2023/09/current-limiting-reactor-series.html)
[ ⌊Complete Guide on Ground Fault Circuit Interrupters⌉GFCI (Ground Fault Circuit Interrupter) – Working, Types, Installing and Troubleshooting](https://studyelectrical.com/2019/03/gfci-ground-fault-circuit-interrupter-breaker.html)
[ ⌊Principle of core balance protection RCCB working⌉How RCCB/ELCB Protects You from Death?](https://studyelectrical.com/2021/11/how-rccb-elcb-protects-you-from-death.html)
[ ⌊Transmission-switching⌉Why Do We Use Transmission Switching in Electricity Supplies?](https://studyelectrical.com/2022/08/why-transmission-switching-in-electricity-supplies.html)
[ ⌊Load break switch with SF6 interrupters⌉Load Break Switches in Electrical Substations](https://studyelectrical.com/2023/08/load-break-switches.html)
[ ⌊Liquid Fuse⌉High Voltage Fuses: Types and Working](https://studyelectrical.com/2023/09/high-voltage-fuses.html)
[ ⌊Basic components of gapped core shunt reactors⌉Shunt Reactors: Types, Working and Design](https://studyelectrical.com/2024/09/shunt-reactors-types-working-and-design.html)
[ ⌊Substation Bus Configurations⌉Substation Bus Configuration / Scheme: The Definitive Guide](https://studyelectrical.com/2019/10/substation-bus-configurations.html)
[ ⌊lightning rod⌉How Does Lightning Rods Work?](https://studyelectrical.com/2023/09/how-does-lightning-rods-work.html)