# How RCCB/ELCB Protects You from Death?

- Link: https://studyelectrical.com/2021/11/how-rccb-elcb-protects-you-from-death.html
- Published: 2021-11-10T14:21:17+00:00
- Author: Tesla

Earthing does not guarantee that humans will be safe when they come into contact
with live conductors. Although [relays ](https://studyelectrical.com/2016/10/basic-relays-electromagnetic-attraction-induction-relays.html)
may be installed to detect earth leakages, typically their settings are high. Therefore,
earth leakage circuit breakers (ELCB) or [residual current circuit breakers (RCCB)](https://studyelectrical.com/2015/05/residual-current-circuit-breakers-elcb-rccb-rcbo-working-principle.html)
are used wherever there is a possibility of human contact with a live conductor.
These breakers work on the core balance current principle.

## Sensitive earth leakage protection

![Principle of core balance protection RCCB working](https://studyelectrical.com/
wp-content/uploads/2021/11/Principle-of-core-balance-protection-RCCB-working.png)

Principle of core balance protection

Figure illustrates the operation of the core balance leakage device. When the system
is under normal conditions, the phase current and neutral current will be equal 
and in phase. Thus, the CT will not detect any current under normal circumstances
since IL + IN = 0 (vector sum).

The ELCB consisting of core balance CT is mounted at the source end. Any time a 
human comes in contact with any part of the line, a portion of the current will 
flow through the body. This will result in an imbalance in the currents entering
and returning to the CBCT of the ELCB. When the fault current flows through the 
human body, IN is reduced by the amount of IF. A relay is triggered by this unbalanced
quantity, and the ELCB is immediately tripped.

It is normal that ELCBs are moulded breakers, similar to miniature circuit breakers,
which are equipped with CBCT inside. It is also common for the CBCT to be mounted
outside, with the unbalanced current being taken to trip a separate relay, the earth
leakage relay.

In the above example, a single-phase system was considered. It is nevertheless the
same principle for three-phase systems with neutral in which the vector sum of the
three phase currents (IR + IY + IB) and the return neutral current IN will also 
be zero. As all phase and neutral conductors are taken in through the CBCT, the 
CBCT does not detect any current under normal conditions. As soon as any leakage
occurs in any phase, the CBCT detects unbalance and trips the breaker.

 There are three levels of sensitivity for the ELCBs: 30 mA, 100 mA, and 300 mA.
ELCBs with 30 mA ratings are recommended for human protection, since currents flowing
above 30 mA can cause serious damage, including death.

### Related posts:

 [ ⌊Transmission-switching⌉Why Do We Use Transmission Switching in Electricity Supplies?](https://studyelectrical.com/2022/08/why-transmission-switching-in-electricity-supplies.html)
[ ⌊Complete Guide on Ground Fault Circuit Interrupters⌉GFCI (Ground Fault Circuit Interrupter) – Working, Types, Installing and Troubleshooting](https://studyelectrical.com/2019/03/gfci-ground-fault-circuit-interrupter-breaker.html)
[ ⌊HRC Fuse⌉Low Voltage Fuses: Types and Examples](https://studyelectrical.com/2023/09/low-voltage-fuses.html)
[ ⌊Generator Reactors⌉Current Limiting Reactor or Series Reactor](https://studyelectrical.com/2023/09/current-limiting-reactor-series.html)
[ ⌊Hydraulic Magnetic Circuit breaker⌉Hydraulic Magnetic Circuit Breaker – Construction, Working and Application](https://studyelectrical.com/2024/03/hydraulic-magnetic-circuit-breaker.html)
[ ⌊Default Thumbnail⌉MCB (Miniature Circuit Breakers) – Types, Working and Trip Curves](https://studyelectrical.com/2014/07/miniature-circuit-breakers-mcb-types-characteristic-curves.html)
[ ⌊Square D Circuit Breaker⌉Square D QO Circuit Breakers](https://studyelectrical.com/2019/02/square-d-qo-circuit-breakers.html)
[ ⌊Auto Reclosing principle⌉Auto Reclosing of Power Lines and Types of Faults](https://studyelectrical.com/2019/02/auto-reclosing-of-power-lines.html)
[ ⌊Liquid Fuse⌉High Voltage Fuses: Types and Working](https://studyelectrical.com/2023/09/high-voltage-fuses.html)
[ ⌊Construction of MCB⌉Thermal Magnetic Circuit Breaker – Construction and Working](https://studyelectrical.com/2024/03/thermal-magnetic-circuit-breaker.html)