# Open Delta (V-V) Connection of Transformers

- Link: https://studyelectrical.com/2019/11/open-delta-v-v-connection-of-transformers.html
- Published: 2019-11-21T15:16:35+00:00
- Author: Tesla

Open Delta Connection is a method of transformer connection used to **transform 
three-phase power using two single-phase transformers**. In this article, you will
learn how this connection is done and the theory behind this.

The Scott connection is another method used for the same purpose of transforming
3 phase power using two single-phase transformers.

Both of these methods result in slightly unbalanced output voltages under load because
of unsymmetrical relations. The unbalance is negligible under usual conditions of
operation.

## Open Delta Connection (V-V Connection)

If one transformer breaks down in a star-star connected system of 3 single-phase
transformers in a [substation](https://studyelectrical.com/2019/04/electrical-substation-equipment-types-components-functions.html),
three-phase power cannot be supplied until the defective transformer has been replaced
or repaired. To eliminate this undesirable condition, single-phase transformers 
are generally **connected in Δ-Δ**.

In this case, if one transformer breaks down, it is possible to continue supplying
three-phase power with the other two transformers because this arrangement maintains
correct voltage and phase relations on the secondary.

However, **with two transformers, the capacity of the bank is reduced to 57.7%**
of what it was with all three transformers in service (i.e., complete Δ-Δ circuit).

### How Open Delta Connection Works?

If one transformer is removed in the Δ-Δ connection of three [single-phase transformers](https://studyelectrical.com/2014/10/parallel-operation-of-single-phase-transformers.html),
the resulting connection becomes open delta or V-V connection.

In complete Δ-Δ connection, the voltage of any one phase is equal and opposite to
the sum of the voltages of the other two phases.

Therefore, under no-load conditions, if one transformer is removed, the other two
will maintain the same three-line voltages on the secondary side.

Under load conditions, the secondary line voltages will be slightly unbalanced because
of the unsymmetrical relation of the impedance drops in the transformers.

![Open Delta Connection in Transformer](https://studyelectrical.com/wp-content/uploads/
2019/11/Open-Delta-Connection-in-Transformer.png)

Open Delta Connection in Transformer

The figure shows an open delta (or V-V) connection; **one transformer shown dotted
is removed**. For simplicity, the load is considered to be star connected.

The figure below shows the **phasor diagram for voltages and currents**.

![Phasor diagram of Open Delta Connected Transformers](https://studyelectrical.com/
wp-content/uploads/2019/11/Phasor-diagram-of-Open-Delta-Connected-Transformers.png)

Phasor diagram of Open Delta Connected Transformers

– V_(AB) , V_(BC, )and V_(CA) represent the line-to-line voltages of the primary.

– V_(ab) , V_(bc, )and V_(ca) represent line-to-line voltages of the secondary.

– V_(an) , V_(bn) and V_(cn) represent the phase voltages of the load.

For inductive load, the load currents I_(a) , I_(b) and I_(c) will lag the corresponding
voltages V_(an) , V_(bn, )and V_(cn) by the load phase angle ϕ.

The transformer windings ab and bc will deliver power given by;

P_(ab) = V_(ab) I_(a) cos(30° + ϕ)

P_(bc) = V_(cb) I_(c) cos(30° – ϕ)

Let, V_(ab) = V_(cb) = V, the voltage rating of transformer secondary winding

I_(a) = I_(c) = I, current rating of the transformer secondary winding

For resistive load  –  power factor = 1    i.e. ϕ = 0°

Power delivered to the resistive load by V-V connection is

**P_(v) = P_(ab )+ P_(bc) = VI cos30° + VI cos30° = 2VI cos30°**

With all the three transformers connected in delta, the power delivered to the resistive
load is

**P_(Δ) = 3VI**

∴ **P_(v)**/**P_(Δ )**= 2VI cos30°/ 3VI = 2 cos30°/ 3** = 0.577**

Hence the **power-handling capacity of a open delta (V-V) circuit** (without [overheating the transformers](https://www.powerlinkoil.com/transformer-oil-causes-of-overheating/))
is **57.7% of the capacity of a complete Δ-Δ circuit** of the same transformers.

In a open delta (V-V) circuit, only **86.6% of the rated capacity** of the two transformers
is available. This can be readily proved.

**Operating Capacity / Available Capacity** = 2VI cos30°/2VI = cos30° = √3/2 = **
0.866**

#### **Example of Open Delta Connection**

Let us illustrate the open delta (V-V) connection with a numerical example.

Suppose three identical single-phase transformers, each of capacity **10 kVA**, 
are connected in Δ-Δ. The total rating of the three transformers is **30 kVA**.

When one transformer is removed, the system reverts to the open delta (V-V) circuit
and can deliver 3-phase power to a 3-phase load.

**However, the kVA capacity of the open delta (V-V) circuit is reduced to 30 x 0.577
= 17.3 kVA and not 20 kVA as might be expected.**

This reduced capacity can be determined in an alternate way.

The available capacity of the two transformers is 20 kVA. When operating in the 
open delta (V-V) circuit, only **86.6% of the rated capacity** is available i.e.
20 x 0.866 = 17.3 kVA.

### Power Factor of Transformers in V-V Circuit

When the open delta circuit is delivering 3-phase power, the [power factor](https://studyelectrical.com/2016/07/what-is-power-factor.html)
of the two transformers is not the same (except at unity p.f.).

Therefore, the voltage regulation of the two transformers will not be the same. 
If the load power factor angle is f, then,

power factor of transformer 1 = cos (30° – ϕ)
power factor of transformer 2 = cos(
30° + ϕ)

**1. When load p.f. = 1 i.e. ϕ = 0°**

In this case, each transformer will have a power factor of 0.866.

**2. When load p.f. = 0.866 i.e. ϕ = 30°**

In this case, one transformer will have a power factor of cos (30° – 30°) = 1 and
the other of cos (30° + 30°) = 0.5.

**3. When load p.f = 0.5 i.e. ϕ = 60°**

In this case, one transformer will have a power factor of cos (30° – 60°) = 0.866
and the other of cos (30° + 60°) = 0.

Thus at a load power factor of 0.5, one transformer delivers all the power at 0.866
power factor and the other (although still necessary to be in the circuit) delivers
no power at all.

### Applications of Open Delta or Open Delta (V-V) Connection

The open delta circuit has a number of features that are advantageous. A few applications
are given below by way of illustration:

 1. The circuit can be employed in an emergency situation when one transformer in a
    complete Δ-Δ circuit must be removed for repair and continuity of service is required.
 2. Upon failure of the primary or secondary of one transformer of a complete Δ-Δ circuit,
    the system can be operated as an open delta (V-V) circuit and can deliver 3-phase
    power (with reduced capacity) to a 3-phase load.
 3. A circuit is sometimes installed as an open delta (V-V) circuit with the understanding
    that its capacity may be increased by adding one more transformer to form a complete
    Δ-Δ circuit. As shown earlier,

**P_(v)**/**P_(Δ)** = 1/√3 = 0.577

**P_(Δ )**= √3 **P_(v)**

Thus if a V-V circuit is changed to complete Δ-Δ circuit, the capacity is increased
by a factor of √3.

### Related posts:

 [ ⌊Transformer Percentage Impedance Testing⌉How to Test Percentage Impedance of Transformer?](https://studyelectrical.com/2019/08/how-to-test-percentage-impedance-of-transformer.html)
[ ⌊Transformer testing at factory⌉Percentage Reactance in Power System (Transformer, Generator or Reactor)](https://studyelectrical.com/2023/01/percentage-reactance-in-power-system-transformer-generator-or-reactor.html)
[ ⌊Generator Reactors⌉Current Limiting Reactor or Series Reactor](https://studyelectrical.com/2023/09/current-limiting-reactor-series.html)
[ ⌊Complete Guide on Ground Fault Circuit Interrupters⌉GFCI (Ground Fault Circuit Interrupter) – Working, Types, Installing and Troubleshooting](https://studyelectrical.com/2019/03/gfci-ground-fault-circuit-interrupter-breaker.html)
[ ⌊Transformer Bushing Types⌉Transformer Bushing Types : RIP Bushing vs OIP Bushing](https://studyelectrical.com/2019/03/transformer-bushing-types.html)
[ ⌊what is connected load⌉What is Connected Load?](https://studyelectrical.com/2021/09/what-is-connected-load.html)
[ ⌊Double end break disconnect switch⌉Disconnect Switches in Substation: Types, Design and Working](https://studyelectrical.com/2022/09/disconnect-switches-types-design-working.html)
[ ⌊Load Curve and Load Duration Curve⌉Load Duration Curve in Power Station](https://studyelectrical.com/2022/09/load-duration-curve-in-power-station.html)
[ ⌊Basic components of gapped core shunt reactors⌉Shunt Reactors: Types, Working and Design](https://studyelectrical.com/2024/09/shunt-reactors-types-working-and-design.html)
[ ⌊Hydrograph⌉Hydrograph: Understanding Components, Types & Applications](https://studyelectrical.com/2025/11/hydrograph-understanding-components-types-applications.html)