An electrical substation is an integral part of a generation, transmission and distribution
system. A substation can interrupt or establish electrical circuit, change the voltage,
frequency or other characteristics of electrical energy flowing in the circuit.

In this article you will learn different types of substations, their functions and
different equipment used used in them.

## What is Substation?

**A substation is an installation that interconnects elements of an electric utility’s
system. These elements can include generators, transmission lines, distribution 
lines, and even neighboring utility systems.**

It is common to refer to the transmission and distribution elements as networks 
or again, as systems.

Depending on the size and complexity of a particular utility system, the transmission
and/or distribution networks may include more than one voltage level.

For instance, a utility’s transmission network may include 115 kV and 230 kV transmission
lines, while another utility’s distribution network may include both 13.8 kV and
34.5 kV distribution lines.

The substation provides the interconnection of transmission circuits and the transformation
between the network of different voltages.

The substation is connected to the network through [overhead lines](https://studyelectrical.com/2016/01/sag-in-overhead-transmission-conductor-lines.html).
In some cases, it may not be possible to make a connection to the substation directly
by the overhead line and [underground cable](https://studyelectrical.com/2014/11/construction-of-underground-cables.html)
entry must be considered.

**Electrical Substations have the following mission to accomplish:**

 * Step-up and step-down voltage transformation
 * Connection of separate transmission and distribution lines into a system to increase
   efficiency and reliability of power supply.
 * Sectionalizing of the power system to increase its reliability and operational
   flexibility – substation called “[switching substation](https://studyelectrical.com/2019/11/switching-station-working-layout.html)”

The different substation configurations are characterized by their [busbar arrangements](https://studyelectrical.com/2019/10/substation-bus-configurations.html)
and generally, any number of circuits may be provided by repeating the pattern.

## Types of Substation

There are many kinds of ac substations. They are classified into different types
based on various criteria. Some of them are discussed below.

**Based on the construction and installation of switchgear**, electric substations
are of two types.

 1. **Air Insulated Switchgear Substation (Open Terminal Substation)**
 2. **Gas Insulated Switchgear Substation (Metal Clad Substation)**

**Based on transmission voltage and function**, the electric substation is classified
into three types.

 1. **Transmission Substation**
 2. **Subtransmission Substation**
 3. **Distribution Substation**

**Based on the installation premises** there are four major types of substations.

 1. **Generating Substation**
 2. **Customer Substation**
 3. **System Station**
 4. **Distribution Station**
 5. **Switching Substation**

![Types of Substation](https://studyelectrical.com/wp-content/uploads/2019/04/Types-
of-Substation.jpg)

Types of Substation

 * **Generating station substations** transform generation voltage (usually 15 kV
   through 23 kV) up to transmission network voltage (usually 69 kV through 500 
   kV).
 * **Transmission switching substations** interconnect portions of the utility system
   transmission network but do not include transformation between voltage levels.
 * **Transmission step-down** (or step-up, depending on your point of view) substations
   interconnect portions of the utility system transmission network and include 
   transformation between transmission network voltage levels.
 * **Distribution step-down substations** may or may not interconnect portions of
   the utility system transmission network, include transformation between transmission
   network and distribution network voltage levels, and interconnect portions of
   the utility system distribution network.
 * **Distribution substations** interconnect portions of the utility system distribution
   network and may include transformation between distribution voltage levels.

**DC interconnections** are made with one of two specialized types of substations.
These dc interconnections are not common and are much higher in capital cost than
comparable ac interconnections.

 1. The first type, ac/dc or dc/ac conversion stations, interconnects the ac transmission
    network of one utility system with a dc transmission line or network. The dc line
    or network connects with one (or more) other conversion stations.
 2. The second type, ac/dc/ac (back-to-back) conversion stations, interconnect the 
    ac transmission network of one utility system with the ac transmission network 
    of another utility system. In effect, this is two conversion stations on the same
    site with the dc transmission line inside the converter building.

### 1. Air Insulated Substation

**Air Insulated Switchgear Substation**, as the name suggests, utilizes primary 
substation equipment whose terminals are in the air.

![AIS Substation Equipments and Power Flow](https://studyelectrical.com/wp-content/
uploads/2019/04/AIS-substation-equipments-or-components.jpg)

AIS Substation Equipments and Power Flow

Consequently, large clearances are required between these terminals and earth and
between terminals of different phases. As a result, the ‘air-insulated / open terminal’
substations occupy relatively large areas of land.

### 2. Gas Insulated Substation

**Gas Insulated Substation** or metal-clad equipment utilizes either solid or gaseous(
SF6) insulation to allow the phase to earth and phase to phase clearance to be drastically
reduced.

![Gas-Insulated-switchgear-Substations-420kV](https://studyelectrical.com/wp-content/
uploads/2019/04/Gas-Insulated-switchgear-Substations-420kV-300x190.jpg)

Gas Insulated Switchgear Substation

The space-saving advantages of gas-insulated/metal-clad equipment can be significant
particularly for high voltage substations in large cities where space is difficult
to obtain and the land is very expensive.

Metalclad equipment may also be attractive for other reasons, notably visual impact
in environmentally sensitive areas and operation in heavily polluted environments.

Air-insulated substations generally cost less than an equivalent gas insulated substation.

Almost all [Gas Insulated Switchgear](https://studyelectrical.com/2017/12/introduction-to-gas-insulated.html)
substations are built indoor. GIS can be easily built underground to avoid any environmental
concern. The internal GIS insulation is independent of atmospheric pressure.

### 3. Transmission Substation

The **transmission substation** transformers support the transmission system and
the smaller sub-transmission and distribution substation transformers.

The transmission substation contains equipment used to sectionalize the electric
transmission system when a fault or short circuit develops on one of the circuits.

[Circuit breakers](https://studyelectrical.com/2018/12/circuit-breaker-operating-principle-and.html)
in the transmission substation are used to switch generating and transmission circuits
in and out of service. The faulted circuit is switched out of service automatically
and de-energized, protecting the remaining portion of the transmission network from
trouble.

![transmission and distribution substation](https://studyelectrical.com/wp-content/
uploads/2019/04/transmission-and-distribution-substation.jpg)

Transmission, Sub transmission and distribution substation

### 4. Sub transmission Substation

Electric substations with equipment used to convert high-voltage, extra-high-voltage(
EHV), or ultra-high-voltage (UHV) transmission lines to the intermediate voltage
sub-transmission lines or to switch sub-transmission circuits operating at voltages
in the range of 34.5 kV to 161 kV are referred to as **sub-transmission substations**.

Sub transmission circuits and substations are located near to high-load concentrations,
usually in urban areas. Sub transmission circuits supply distribution substations.

### 5. Distribution Substation

Substations located in the middle of a load area are called **distribution substations**.
These substations may be as close together as 2 miles in densely populated areas.

The substations contain power transformers that reduce the voltage from sub-transmission
levels to distribution levels, usually in the range of 4.16Y/2.4 kV to 34.5Y/19.92
kV.

The transformers are normally equipped to regulate the substation bus voltage. Circuit
breakers or [circuit reclosers](https://studyelectrical.com/2019/02/auto-reclosing-of-power-lines.html)
in the distribution substations are installed between the low-voltage bus and the
distribution circuits.

The distribution circuits vary in capacity from approximately 5 MVA to 20 MVA (1
MVA = 1000 kVA).

Large distribution substations have power transformers with a capacity as large 
as 100 MVA and serve as a source to as many as 10 distribution circuits. Read the
difference between [power transformers and distribution transformers](https://studyelectrical.com/2014/05/difference-between-power-transformer.html).

If the power transformers do not have automatic tap-changing underload equipment,
it is usually necessary to install voltage regulators.

These above-mentioned substations are explained in [major types of substations](https://studyelectrical.com/2018/11/4-major-types-of-electrical-substations.html).

| Substation Type | Description | 
| Air Insulated Switchgear Substation | Utilizes primary substation equipment with terminals in the air. Requires large clearances and occupies significant land area. | 
| Gas Insulated Switchgear Substation | Uses solid or gaseous (SF6) insulation, reducing clearances and saving space, suitable for high voltage substations in urban areas. | 
| Transmission Substation | Supports the transmission system and sectionalizes circuits during faults. Contains circuit breakers for switching circuits. | 
| Subtransmission Substation | Converts high-voltage transmission lines to intermediate voltage sub-transmission lines or switches sub-transmission circuits. | 
| Distribution Substation | Located in load areas, reduces voltage to distribution levels. Contains power transformers, circuit breakers, and voltage regulation. |

## Functions of a Substation

A substation performs a major role in our power system. The functions of a substation
may include one or more of the following:

 * To **isolate a faulted element** from the rest of the utility system.
 * To allow an element to be **disconnected from the rest of the utility system**
   for maintenance or repair.
 * To **change or transform voltage levels** from one part of the utility system
   to another.
 * To **control power flow** in the utility system by switching elements into or
   out of the utility system.
 * To **provide sources of reactive power** for power factor correction or voltage
   control.
 * To **provide data concerning system parameters** (voltage, current flow, power
   flow) for use in operating the utility system.

## Substation Equipment / Components

An electrical substation contains many types of equipment. Substation generally 
comprises the following equipment:

 1.  [**Power Transformers**](https://studyelectrical.com/2014/05/difference-between-power-transformer.html)
 2.  **Tap Changing Equipment**
 3.  [**Circuit Breakers**](https://studyelectrical.com/2018/12/circuit-breaker-operating-principle-and.html)
 4.  [**BusBar, Bays and Steel Structures**](https://studyelectrical.com/2019/10/substation-bus-configurations.html)
 5.  [**Lightning Arrester**](https://studyelectrical.com/2014/06/lightning-arrester-location-rating-and.html)
 6.  **Circuit Switchers**
 7.  [**Disconnect Switch / Isolator**](https://studyelectrical.com/2022/09/disconnect-switches-types-design-working.html)
 8.  **[Earth Switches](https://studyelectrical.com/2023/09/high-speed-grounding-switches.html)**
 9.  [**Current Transformer**](https://studyelectrical.com/2018/09/current-transformer-ct-construction-working-operating-principle-advantages-uses.html)
 10. **Potential Transformer**
 11. **Neutral Grounding Resistor**
 12. **[High Voltage Fuses](https://studyelectrical.com/2023/09/high-voltage-fuses.html)**
 13. **Metal-Clad Switchgear**
 14. **Shunt Reactors**
 15. **[Current-Limiting Reactor or Series Reactor](https://studyelectrical.com/2023/09/current-limiting-reactor-series-reactor.html)**
 16. **Line Trap**
 17. [**Coupling Capacitor Voltage Transformer**](https://studyelectrical.com/2014/03/capacitor-voltage-transformer.html)
 18. **Control House**
 19. **Control Panel**
 20. [**Substation Protective Relays**](https://studyelectrical.com/2015/08/how-protective-electrical-relays-work.html)
 21. **Supervisory Control**
 22. **Remote Terminal Unit**
 23. **Digital Fault Recorder**
 24. **Capacitor Bank**
 25. **Voltage Regulator**
 26. **Power-Line Carrier Equipment**
 27. **Microwave Equipment**
 28. **Batteries**

To fulfill the function of a substation, they include a wide variety of equipment.
Each of them will be explained in the next subsections.

![Components of an air insulated substation](https://studyelectrical.com/wp-content/
uploads/2019/04/components-air-insulated-substation.jpg)

Components of an air-insulated substation

### Power Transformers

Power transformers are the most important equipment in an electrical substation.
They are [different from distribution transformers](https://studyelectrical.com/2014/11/power-transformers-and-distribution-transformers.html).

They perform different functions. They are used to

 * **change the voltage from one level to another,**
 * **to regulate the voltage level,**
 * **and to control the flow of reactive kilovolt-amperes in the power system.**

Power transformers installed in transmission substations will normally be constructed
for and operate at voltages in the range of 138,000 volts to 765,000 volts or higher.

Most substations will have three-phase transformers. Some substations will have 
three [single-phase transformers in parallel](https://studyelectrical.com/2014/10/parallel-operation-of-single-phase-transformers.html)
installed in a bank.

![Three phase transformer](https://studyelectrical.com/wp-content/uploads/2019/04/
Three-phase-transformer.jpg)

Three Phase Transformer in a Substation

Often, a fourth single-phase transformer will be located at the substation to serve
as a spare. If one of the transformers connected in the bank fails, the spare is
energized to expedite the restoration of electric service.

![Three single phase tranformers in bank](https://studyelectrical.com/wp-content/
uploads/2019/04/Three-single-phase-tranformers-in-bank.jpg)

Three Single Phase Transformer in Bank

The capacity of the transmission substation transformers will normally be in the
range of 1,000 MVA to 50 MVA.

Power transformers installed in distribution substations will normally be constructed
for and operate at the lower voltages and smaller capacities. The voltages will 
generally be in the range of 161,000 volts to 4,160 volts and the capacities in 
the range of 50 MVA to 5 MVA. 

The figure given is a picture of a power transformer that is part of a distribution
substation.

### Tap Changing Equipment

Optional equipment that may be added to the substation transformer is tap changing
equipment.

There are two types of tap changers.

 1. On load tap changer
 2. Off load tap changer

**The tap changer feature allows the voltage to be adjusted in increments as system-
loading conditions require.**

![Transformer Tap Changer](https://studyelectrical.com/wp-content/uploads/2019/04/
Transformer-Tap-Changer.jpg)

Tap Changer mounted on a Transformer

The controls of the tap changing equipment are installed in a panel mounted on the
side of the power transformer. Remote control of the tap changing equipment is usually
installed as well.

### Circuit Breakers

High Voltage and [Medium-voltage switchgear](https://studyelectrical.com/2015/07/what-is-switchgear-features-components-hv-mv-lv.html)
such as [oil circuit breaker](https://studyelectrical.com/2016/06/oil-circuit-breakers-types-working-construction.html),
[SF6 circuit breaker](https://studyelectrical.com/2014/07/sulphur-hexaflouride-sf6-circuit-breaker-construction-working-advantages.html),
[air circuit breaker](https://studyelectrical.com/2014/12/working-of-air-circuit-breakers.html),
gas circuit breaker, and [vacuum circuit breakers](https://studyelectrical.com/2014/11/vacuum-circuit-breaker-vcb-working-construction.html)
are used to switch electric circuits and substation equipment in and out of the 
system.

**A circuit breaker is a mechanical switching device, capable of making, carrying
and breaking currents under normal circuit conditions and also making, carrying 
for a specified time and breaking currents under specified abnormal circuit conditions
such as those of short circuit.**

The contacts of the circuit breakers are opened and closed by mechanical linkages
manufactured from insulating materials and utilizing energy from compressed air,
electric magnets, or charged springs.

![Hybrid Circuit Breaker](https://studyelectrical.com/wp-content/uploads/2019/04/
Hybrid-Circuit-Breaker.jpg)

A Hybrid Circuit Breaker. (This adopts a conventional air-insulated way of busbar
connection to GIS. This smartly overcome the disadvantages of conventional AIS equipment)

Some of the high-voltage circuit breakers utilize compressed air to operate the 
contacts and interrupt the current flow when the contacts are open.

Operation of the circuit breakers is initiated, utilizing dc circuits, by manually
operating a switch, by remote operation of supervisory control equipment, or by 
relays that automatically recognize predetermined abnormal conditions or electrical
failures in the system.

Various [types of circuit breakers](https://studyelectrical.com/2014/05/classification-types-of-circuit-breakers.html)
used in high voltage substations are.

 1. **[SF6 Circuit Breaker](https://studyelectrical.com/2014/07/sulphur-hexaflouride-sf6-circuit-breaker-construction-working-advantages.html)**
 2. **[Oil Circuit Breaker](https://studyelectrical.com/2016/06/oil-circuit-breakers-types-working-construction.html)**
 3. **[Air Blast Circuit Breaker](https://studyelectrical.com/2014/05/air-blast-circuit-breakers.html)**
 4. **[Vacuum Circuit Breaker](https://studyelectrical.com/2014/11/vacuum-circuit-breaker-vcb-working-construction.html)**

There are low voltage circuit breakers like [MCB](https://studyelectrical.com/2014/07/miniature-circuit-breakers-mcb-types-characteristic-curves.html)
and [GFCI](https://studyelectrical.com/2019/03/gfci-ground-fault-circuit-interrupter-breaker.html)
that are not normally used in high voltage substations. MCBs are used inside the
control panels.

### BusBar, Bays and Steel Structures

**The substation buses are current-carrying devices that interconnect the individual
pieces of substation equipment.**

![Busbar in HV Substation](https://studyelectrical.com/wp-content/uploads/2019/04/
Busbar-in-substation.jpg)

Busbar in HV Substation

The substation bus tubing (or bus bar) is aluminum or copper. Steel structures provide
support for insulators, which are used to terminate lines, and support buses.

Disconnect switches and other equipment are mounted on the steel structures.

Read more about [busbar configuration in a substation](https://studyelectrical.com/2019/10/substation-bus-configurations.html).

### Lightning Arrester

The lightning arresters are another important substation switchgear equipment that**
protects the electric system and the substation equipment from lightning strikes
and switching surges.**

The [lightning arresters](https://studyelectrical.com/2014/06/lightning-arrester-location-rating-and.html)
are installed in a substation near the termination of aerial circuits and close 
to the more valuable pieces of equipment, such as power transformers.

![Lightning Arrester](https://studyelectrical.com/wp-content/uploads/2019/04/Lightning-
Arrester.jpg)

Lightning Arrester

The power transformer has lightning arresters mounted on the radiators which are
connected to both the 345 kV and 138 kV transformer bushings.

Lightning arresters contain semiconductor blocks, which limit the magnitude of high-
surge voltages, permit the large-surge currents to pass harmlessly to the ground,
and interrupt the power-follow current after the surge is eliminated.

Metal-oxide surge arresters function like a [ceramic capacitor](https://studyelectrical.com/2016/12/different-types-classification-of-capacitors.html)
at normal line voltage, limiting the flow of current to ground.

When a high voltage begins to build up across the semiconductor blocks, they provide
a low-impedance path to ground, which permits the surge current to flow to ground,
limiting the voltage buildup and preventing the equipment from being damaged. The
semiconductor blocks in the arresters are manufactured using zinc oxide material.

### Circuit Switchers

**According to IEEE, Circuit Switcher is a mechanical switching device with an integral
interrupter, suitable for making, carrying, and interrupting currents under normal
circuit conditions.**

Circuit switchers are also known as load interrupter switch or line circuit breaker.

Circuit switcher is a device that combines a disconnect switch with an SF6 interrupter.
This device has the ability to switch electrical loads (energized circuits) and 
limited fault current interrupting capability. In a single device, it offers isolation
and limited fault interrupting capability.

![Circuit Switcher used for protecting transformers](https://studyelectrical.com/
wp-content/uploads/2019/04/Circuit-Switcher.jpg)

Circuit Switcher used for protecting transformers

If the voltage is less than 500 kV, circuit switchers usually have a common structure
supporting three phases (AC). For voltages above 500 kV, a common structure is too
wide, and each phase has its own structure. A control junction box and operating
mechanism are supported by structure legs.

The circuit switcher imparts a dynamic load when it opens or closes, and the structure
should be rigid enough to allow proper switching.

It is also suitable for interrupting specified short-circuit current that may be
less than its close and latch, momentary, and short-time current ratings.

Circuit switchers employ SF6 puffer-type interrupters for switching and protection
of transformers, lines, cables, and capacitor banks and have fault-interrupting 
ratings suitable for use in protecting medium- to large load transformers. Models
are available with and without integral disconnect switches.

**Circuit Switcher vs Circuit Breaker**

Now you may be confused about the difference between [Circuit Breaker](https://studyelectrical.com/2018/12/circuit-breaker-operating-principle-and.html)
and Circuit Swither. Circuit Switchers are different from the circuit breakers. 
Circuit switcher is an economic solution adopted for switching substation equipment(
eg: transformer). They are cheaper and generally have a lower interruption rating
compared to circuit breakers.

Circuit switchers are typically used on distribution transformer primaries where
[fuses](https://studyelectrical.com/2017/09/what-is-fuse-and-how-it-works.html) 
were typically used in the past. The use of a circuit switcher in place of fuses
is a major improvement in protection. For most of these applications, there is no
way that the cost of a 115 kV or 230 kV circuit breaker could be justified.

_The circuit switcher has the following benefits over circuit breaker_: Compact,
low cost, and some models include a visible break switch in their operation.

Drawbacks over a circuit breaker include low-speed reclosing, and not designed for
high-operation environments.

The operation of circuit switchers is initiated by manually operating a switch, 
by remote supervisory control equipment, or by substation protective relays that
automatically sense abnormal predetermined system or equipment conditions or electrical
failures (faults).

Circuit switchers serve to provide reliable, economical switching and protection
for transformers, single-shunt capacitor banks, line-connected, and testing connected
shunt reactors, lines, and cables.

### Disconnect Switch / Isolator

**[Disconnect switches](https://studyelectrical.com/2022/09/disconnect-switches-types-design-working.html)(
Isolators) are devices that are generally operated off-load to provide isolation
of main plant items for maintenance, on to isolate faulted equipment from other 
live equipment.**

Air Insulated or open terminal disconnectors are available in several forms for 
different applications.

At the lower voltages, single break types are usual with either ‘rocker’ type or
single end rotating post types being predominant.

![disconnector-switches-substation](https://studyelectrical.com/wp-content/uploads/
2019/04/disconnector-switches-substation.jpg)

Disconnect Switch / Isolator

At higher voltages, rotating center post, double end rotating post, vertical break,
and pantograph type disconnectors are more common. [Air break switches](https://studyelectrical.com/2015/09/air-break-switch-types-operation-working.html)
are used in lower voltage to disconnect on load.

Disconnectors are usually interlocked with the associated circuit breaker to prevent
any attempt being made to interrupt load current. Disconnectors are not designed
to break fault current although some designs will make fault current.

Most disconnectors are available with either a manual drive mechanism or motor operated
drive mechanism and the appropriate drive method must be selected for a particular
disconnector in a particular substation.

For example, in a remotely controlled unmanned double busbar substation the busbar
selector disconnectors would be motor operated to allow ‘on load’ busbar changes
without a site visit being required.

Disconnector mechanisms incorporate a set of auxiliary switches for remote indication
of disconnector position, electrical interlocking and current transformer switching
for busbar protection.

### Earth Switches

**Earthing switches** are usually associated and interlocked with disconnectors 
and mounted on the same base frame. They are driven by a separate, but similar, 
mechanism to that used for the disconnector.

This arrangement avoids the need for separate post insulators for the earth switch
and often simplifies interlocking.

![Earthing Switch](https://studyelectrical.com/wp-content/uploads/2019/04/Earth-
Switch.jpg)

Earthing Switch

Normally earth switches are designed to be applied to dead and isolated circuits
and do not have a fault making capability, however special designs are available
with fault making capability if required.

One practical point worth noting is that line or cable circuit earth switches are
normally interlocked with the local line disconnector, but reliance is placed on
operating procedures to ensure that the circuit is isolated at the remote end before
the earth is applied.

### Current Transformer

**A current transformer (CT) is a type of transformer that is used to measure AC.
It produces an alternating current (AC) in its secondary which is proportional to
the AC current in its primary.**

The [Current Transformer](https://studyelectrical.com/2018/09/current-transformer-ct-construction-working-operating-principle-advantages-uses.html)
is one of the substation equipment used to convert the primary power signal to manageable
values for metering systems, recording systems, protective relay systems, power 
generation, plant monitoring systems, SCADA and load control.

Current transformers are used extensively for measuring current and monitoring the
operation of the power grid.

![Current transformer](https://studyelectrical.com/wp-content/uploads/2019/04/Current-
transformer.jpg)

Current transformer

The primary winding of a current transformer is connected in series with the high-
voltage conductor. The magnitude of amperes flowing in the high-voltage circuit 
is reduced proportionately by the ratio of the transformer windings.

The secondary winding of the current transformer is insulated from the high voltage
to permit it to be connected to low-voltage metering circuits.

Current and potential transformers supply the intelligence for measuring power flows
and the electrical inputs for the operation of protective relays associated with
the transmission and distribution circuits or equipment such as power transformers.

Read more on [Current Transformers.](https://studyelectrical.com/2018/09/current-transformer-ct-construction-working-operating-principle-advantages-uses.html)

### Potential Transformer

**High voltages in the substation are measured by reducing the voltage proportionately
with equipment called a potential transformer.**

Its high-voltage winding connected to the transmission or distribution circuit and
its low-voltage winding connected to a meter or relay or both.

![Voltage Transformer](https://studyelectrical.com/wp-content/uploads/2019/04/voltage-
transformer.jpg)

Voltage Transformer

Potential transformers are required to provide accurate voltages for meters used
for billing industrial customers or connecting utility companies. If single-phase
transformers are used, three transformers are generally required to measure power
on a three-phase circuit.

## Neutral Grounding Resistor

The neutral grounding resistor provides resistance grounding of the neutral transformers
to limit ground fault current to a value that does not damage generating, distribution,
or other associated equipment in the power system, yet allows sufficient flow of
fault current to operate protective relays to clear the fault.

![Neutral grounding resistor](https://studyelectrical.com/wp-content/uploads/2019/
04/Neutral-grounding-resistor.jpg)

Neutral grounding resistor

With solid grounding, the system is directly grounded, and the fault current is 
limited only by the soil resistance. Fault currents can be very high, causing damage
to transformers, generators, motors, wiring, and other equipment. A Neutral Grounding
Resistor is inserted between neutral and ground in order to increase the net resistance
in the event of an earth fault, thus limiting the current.

Neutral Grounding Resistors are sometimes mounted on separate structures but are
usually mounted on the transformer tank.

### High-Voltage Fuses

High-voltage fuses are used in substations to protect the electrical system from
faults in such equipment as potential transformers or power transformers.

![115 kV High voltage power fuse](https://studyelectrical.com/wp-content/uploads/
2019/04/115-kV-High-voltage-power-fuse.jpeg)

115 kV High voltage power fuse

A group operated high-voltage disconnect switch and three power fuses are mounted
on the terminal structure.

The [fuses](https://studyelectrical.com/2017/09/what-is-fuse-and-how-it-works.html)
are connected in series with the power transformer that serves as a source for the
[switchgear](https://studyelectrical.com/2015/07/what-is-switchgear-features-components-hv-mv-lv.html).

### Metal-Clad Switchgear

According to [IEEE standard C37.20.2](http://ieeexplore.ieee.org/document/7279038),
in Metal Clad Switchgear, the main switching and interrupting device is of the removable(
drawout) type arranged with a mechanism for moving it physically between connected
and disconnected positions.

 They are equipped with self-aligning and self-coupling primary disconnecting devices
and disconnectable control wiring connections.

![Metal Clad Switchgear](https://studyelectrical.com/wp-content/uploads/2019/04/
Metal-Clad-Switchgear.jpg)

Metal Clad Switchgear

Outdoor metal-clad switchgear provides a weatherproof housing for [circuit breakers](https://studyelectrical.com/2018/12/circuit-breaker-operating-principle-and.html),
[protective relays](https://studyelectrical.com/2015/08/how-protective-electrical-relays-work.html),
meters, [current transformers](https://studyelectrical.com/2018/09/current-transformer-ct-construction-working-operating-principle-advantages-uses.html),
potential transformers, bus conductors, and other items necessary to provide electric-
system requirements.

Indoor [switchgear](https://studyelectrical.com/2015/07/what-is-switchgear-features-components-hv-mv-lv.html)
must be installed in a building for protection from the elements.

For the typical 13.2–7.6 kV distribution substation, the [switchgear](https://studyelectrical.com/2015/07/what-is-switchgear-features-components-hv-mv-lv.html)
consists of a 2,000A bus and six (6) breaker cells. The breaker cells are one 2,000A
main breaker, four 1,200A feeder breakers, and one 2,000A future bus-tie breaker
that will serve as the mobile sub connection. One of the feeder cells is equipped
with a capacitor bank isolation switch.

### Shunt Reactors

When the capacitive reactance from extra-high-voltage transmission-line circuits
exceeds the ability of the system to absorb the reactive kVA (kiloVars), shunt reactors
are installed.

![Shunt reactor in substation](https://studyelectrical.com/wp-content/uploads/2019/
04/shunt-reactor-in-substation.jpg)

Shunt reactor in substation

**A shunt reactor compensates for the shunt capacitance and the charging current
drawn by a transmission line.** In the absence of compensation for charging current,
the voltage at the receiving end of a long transmission line can exceed the voltage
at the sending end by as much as 50%.  

The shunt reactor is supported directly on a foundation.

The shunt reactor shown in the figure is a three-phase single-winding transformer.
It serves as an inductive reactance on the power system, neutralizing capacitive
reactance associated with the long extra-high-voltage transmission line.

Shunt reactors are usually located in substations and connected to a transmission
line terminal through a [disconnect switch](https://studyelectrical.com/2022/09/disconnect-switches-types-design-working.html).

### Current-Limiting Inductor or Air Core Reactor

The purpose of a current-limiting inductor is to limit the amount of short-circuit
current that can flow in a circuit by adding inductive reactance to it.

![Air Core Shunt Reactor](https://studyelectrical.com/wp-content/uploads/2019/04/
Air-Core-Shunt-Reactors.jpg)

Air Core Reactor

Dry inductors are typically used for current-limiting applications and do not usually
include electromagnetic shielding. These inductors have a magnetic field surrounding
them under normal conditions, which becomes stronger when they carry short-circuit
current. The magnetic field of these inductors interacts with the field of other
inductors when they are too close together. When metallic objects are placed in 
the magnetic field of an inductor, the magnetic field induces eddy currents. However,
currents are induced in any closed conductive loops located within the inductor’s
magnetic field.

To maintain the manufacturer’s recommended magnetic clearance and necessary personnel
clearance, dry current-limiting inductors are usually supported on insulators and
aluminum or fiberglass pedestals. The supporting pedestals are bolted directly to
the foundation.

### Line Trap

Line traps (also known as wave traps) present high impedance to carrier frequencies
but negligible impedance to normal 60Hz or 50Hz line currents. It is a blocking 
filter that is used to restrict the carrier signal to the transmission line on which
it is installed. This is done to prevent the carrier signal from entering substation
equipment.

The line trap can be installed vertically or horizontally on either a single or 
multiple pedestal support structure. They have also been mounted with one end of
the line trap supported by a coupling capacitor or [coupling capacitor voltage transformer](https://studyelectrical.com/2014/03/capacitor-voltage-transformer.html)
and the other end by an insulator. The line trap can also be suspended from a structure

### Coupling Capacitor Voltage Transformer

At voltages above about 100 kV (phase) the conventional electromagnetic type of 
potential transformer becomes expensive owing to insulation requirements. A less
expensive alternative is Capacitive Voltage Transformer.

Communication signals in the form of high-frequency voltages are transmitted to 
the transmission lines through coupling capacitors.

Some of the coupling capacitors are equipped with potential devices which make it
possible to measure the voltage on transmission-line circuits.

The coupling capacitor potential devices are accurate enough to be used for supplying
voltages to protective relays but—unless they are specifically compensated —not 
accurate enough to supply voltages for meters designed for billing purposes.

![Capacitor Voltage Transformer](https://studyelectrical.com/wp-content/uploads/
2019/04/capacitor-voltage-transformer.jpg)

Capacitor Voltage Transformer

The figure above shows a [coupling capacitor voltage transformer](https://studyelectrical.com/2014/03/capacitor-voltage-transformer.html)(
CVT or CCVT).

### Control House

The substation control house is used to protect the control equipment, including
switchboard panels, batteries, battery chargers, supervisory control, power-line
carrier, meters, and relays, from the elements.

Underground and overhead conduits and control wire are installed to connect the 
controls of all the equipment in the substation to the control panels normally installed
in the control house.

Each substation usually contains several thousand feet of conduit and miles of the
control wire.

### Control Panel

The control panels installed in a control house provide mountings for meters, relays,
switches, indicating lights, and other control devices.

![control panel](https://studyelectrical.com/wp-content/uploads/2019/04/control-
panel.jpg)

Engineer checking status of switchgear from the control panel

### Substation Protective Relays

Substation protective relays installed on control panels are used to sense electrical
failures on transmission and distribution circuits or in pieces of substation equipment,
such as power transformers, substation bus, reactors, capacitors, and circuit breakers.

![Substation Relay](https://studyelectrical.com/wp-content/uploads/2019/04/Substation-
Relay.jpg)

Substation Relay

Some relays are used to supervise, monitor, and perform predetermined operations
as required by system conditions.

Relays automatically operate their contacts to properly identify the source of trouble
and remove it from the electrical system.

Protective relay systems provide overcurrent, differential current, overvoltage,
under voltage, over frequency, under frequency, directional, and distance protection.

### Supervisory Control

The **supervisory control equipment** permits the remote control of substations 
from a system control center or other selected point of control.

![Supervisory Control Center](https://studyelectrical.com/wp-content/uploads/2019/
04/supervisory-control-substation.jpg)

Supervisory Control Center

Distribution substations are normally unattended and operate automatically or are
controlled remotely by supervisory control equipment from a central control center.

Supervisory control equipment is used to open and close circuit breakers, operate
tap changers on power transformers, supervise the position and condition of equipment,
and telemeter the quantity of energy flowing in a circuit or through a piece of 
equipment.

### Remote Terminal Unit

The **remote terminal unit (RTU**) is the interface between the supervisory control
and the substation equipment.

The RTU is a monitor and transmitter of the substation and electric system data.

![Remote terminal unit](https://studyelectrical.com/wp-content/uploads/2019/04/Remote-
terminal-unit.jpg)

Remote terminal unit

The Remote Terminal Unit (RTU), shall be installed at Substations **to acquire analog
data and digital data**.

 * **Analog data** includes KW export, KW import, frequency, OLTC, power factor,
   maximum demand, planned outage duration & numbers, forced outage duration & numbers,
   electricity consumed locally, MVA capacity of Sub-Station, length of Transmission
   lines, etc.
 * **Digital data** include the status of isolators, circuit breakers, etc. at each
   Sub-Station under this scope of work and transfer those information to the data
   server at the supervisory control center and back-up supervisory control center.

### Digital Fault Recorder

The **digital fault recorder** records fault data and provides an accurate sequence
of events for system disturbances on the electric system.

![Digital_fault_recorder](https://studyelectrical.com/wp-content/uploads/2019/04/
Digital_fault_recorder.jpg)

Digital fault recorder

A digital fault recorder (DFR), is an IED that records information about power system
disturbances. It is capable of storing data in a digital format when triggered by
conditions detected on the power system.

Harmonics, frequency, and voltage are examples of data captured by DFRs.

### Capacitor Bank

Capacitor banks are used to maintain or increase voltages in power lines and reduce
inductive losses, thereby improving efficiency of the power system.

After the capacitor bank is installed, the outer periphery of the bank should be
enclosed inside a fence for protection of personnel, if electrical clearance is 
not provided.

![capacitor-bank](https://studyelectrical.com/wp-content/uploads/2019/04/capacitor-
bank.jpg)

Capacitor Bank

Reactive kilovolt-amperes can be supplied to the electrical system by connecting**
banks of capacitors** to the distribution circuits in substations or out on the 
distribution lines to neutralize the effect of customer-inductive loads.

Capacitors used in this manner help to control voltages supplied to the customer
by eliminating the voltage drop in the system caused by inductive reactive loads.

Capacitors in distribution substations are usually mounted in metal cubicles. The
capacitors, mounted on the racks in the cubicles, are usually single-phase, single-
bushing units rated 100-kVAR through 400-kVAR capacitance, 60 Hz, and a voltage 
consistent with the distribution system.

They are connected between each of the three-phase conductors and ground. Capacitor
units for the higher distribution voltages and those connected to conductors energized
at transmission voltages are normally mounted on open-type racks.

The capacitor units are connected in series and cascaded to provide equipment that
can be connected to the higher voltage distribution and transmission systems.

### Voltage Regulator

The **voltage regulator**s maintain the system voltage on the distribution circuits.
As settings on the voltage regulators are adjusted for various load conditions that
occur, the desired voltage is obtained.

### Power-Line Carrier Equipment

The **power-line carrier equipment** provides high-frequency voltages to be used
for transmitting voice communications or telemetered signals on high-voltage transmission-
line circuits.

![Power line carrier equipment](https://studyelectrical.com/wp-content/uploads/2019/
04/Power-line-carrier-equipment.png)

Power line carrier equipment

In the case of voice communications, the sound frequency modulates a high-frequency
signal connected to the transmission-line circuit using coupling capacitors.

This equipment permits using the line conductors for communication, relaying, supervisory
control, and metering in addition to the transmission of electric power.

### Microwave Equipment

Radio signals used for point-to-point [communications between substations](https://electrical-engineering-portal.com/download-center/books-and-guides/power-substations/substation-communication-systems)
or other power-system facilities operating in the megahertz frequencies are called
microwave.

The frequencies range from 952 MHz to 13,000 MHz or higher. Microwave radio signals
are used for communication channels, protective relaying, supervisory control, and
remote metering.

### Batteries

Control batteries supply energy to operate circuit breakers and other equipment.

![substation battery bank](https://studyelectrical.com/wp-content/uploads/2019/04/
substation-battery-bank.jpg)

Substation battery bank

It is necessary to use dc control systems with a storage battery as a source to 
make it possible to operate equipment during periods of system disturbances and 
outage.

Battery chargers are used to automatically keep the batteries charged completely
to provide sufficient emergency power for all necessary operations.

### Related posts:

 [ ⌊Transformer Bushing Types⌉Transformer Bushing Types : RIP Bushing vs OIP Bushing](https://studyelectrical.com/2019/03/transformer-bushing-types.html)
[ ⌊Transformer Percentage Impedance Testing⌉How to Test Percentage Impedance of Transformer?](https://studyelectrical.com/2019/08/how-to-test-percentage-impedance-of-transformer.html)
[ ⌊Transformer testing at factory⌉Percentage Reactance in Power System (Transformer, Generator or Reactor)](https://studyelectrical.com/2023/01/percentage-reactance-in-power-system-transformer-generator-or-reactor.html)
[ ⌊Generator Reactors⌉Current Limiting Reactor or Series Reactor](https://studyelectrical.com/2023/09/current-limiting-reactor-series.html)
[ ⌊PD Testing Guide⌉Guide To Becoming An Expert In Partial Discharge Testing](https://studyelectrical.com/2024/01/partial-discharge-testing-guide.html)
[ ⌊Delta delta connection⌉Delta-Delta (Δ–Δ) Transformer Connection: Advantages, Working, and Application](https://studyelectrical.com/2025/07/delta-delta-%ce%b4-%ce%b4-transformer-connection-advantages-working-and-application.html)
[ ⌊Delta delta connection of transformer⌉Three-Phase Transformer Connections: Y–Y, Δ–Δ, Y–Δ, Δ–Y, V–V, T-T](https://studyelectrical.com/2025/07/three-phase-transformer-connections-y-y-%ce%b4-%ce%b4-y-%ce%b4-%ce%b4-y-v-v-t-t.html)
[ ⌊Featured image for StudyElectrical.com article explaining why transformers are rated in kVA not kW. The technical illustration shows a dynamic central transformer labeled 'RATED IN kVA' glowing with electric blue and gold energy, flanked by icons representing a resistive heater load (cosφ = 1.0) and an inductive motor load (cosφ = 0.8). Swirling equations and circuit diagrams surround the unit. The StudyElectrical logo is in the bottom corner.⌉Why Transformers are Rated in kVA, Not in kW? (With Proof)](https://studyelectrical.com/2014/08/why-transformers-are-rated-in-kva-not-in-kw.html)