# Transformer Bushing Types : RIP Bushing vs OIP Bushing

- Link: https://studyelectrical.com/2019/03/transformer-bushing-types.html
- Published: 2019-03-30T18:43:13+00:00
- Author: Tesla

![Transformer Bushing Types](https://studyelectrical.com/wp-content/uploads/2019/
03/Transformer-Bushing-Types.jpg)

Transformer bushing types are categorized based on their material, manufacturing,
and design mainly into the following types:

 1. OIP (Oil-Impregnated Paper) Bushing
 2. RIP (Resin Impregnated Paper) Bushing
 3. RIS (Resin Impregnated Synthetic) Bushing
 4. Resin Bonded Paper (RBP) Bushing
 5. Cast Epoxy Bushing

You can read about all other types of electrical bushings in [Electrical Bushings – Types, Purpose, and Construction.](https://studyelectrical.com/2015/09/electrical-bushings-types-and-purpose-classification-construction.html)

A transformer bushing is one [electrical bushing](https://studyelectrical.com/2015/09/electrical-bushings-types-and-purpose-classification-construction.html)
that enables one or several conductors to pass through the grounded transformer 
tank and insulates the conductor from it.

Bushings are a very vital component of transformers. Based on _CIGRE WG-12 Report-
1983_, Bushings (14%) are the 3rd major source of transformer failure after On Load
Tap Changer (40%) & Winding (35%).

Broadly EHV class bushings can be categorized in the following two types based on
their material, manufacturing & design:

This article focuses mainly on the main two transformer bushing types namely Oil
impregnated Bushing and Resin impregnated Bushings and their comparison.

## Oil Impregnated Paper (OIP) Transformer Bushing

The traditional Oil Impregnated Paper (OIP) bushing technology as a transformer 
bushing types uses oil as its basic insulating medium.

Use of oil has many severe drawbacks in bushing life, such as being susceptible 
to moisture ingress and oil leakage due to worn out seals.

In turn, a greater vulnerability in an OIP transformer bushing type exists to lightning
strikes or other factors that can trigger explosive failure. Additionally, excessive
filling of oil reservoirs in horizontal mount applications can lead to severe operational
problems.

Unusually high operating temperatures on an OIP bushing can comprise its bushing
life and again lead to severe operational problems.

![Oil Impregnated paper transformer bushing types](https://studyelectrical.com/wp-
content/uploads/2019/03/Oil-Impregnated-paper-transformer-bushing-types.jpg)

 Construction of an oil impregnated paper bushing of a transformer

The figure shows the cross-sectional view of OIP Bushing.

In OIP bushing the core is wound from paper and subsequently treated and impregnated
with an insulating liquid, generally transformer oil.

The core is contained in an insulating envelope (generally “Porcelain”), the space
between the core and the insulating envelope being filled with the same insulating
liquid as that used for impregnation.

Bushings are also provided with Oil level gauge & Test Tap. In the center stem is
provided which connects the Overhead conductor to transformer winding, this is usually
made of copper.

## Resin Impregnated Paper (RIP) Bushing

Recently a revolutionary new class of insulating material called resin impregnated
paper (RIP) with superior thermal and electrical performance has been developed.

![Resin Impregnated paper bushing construction](https://studyelectrical.com/wp-content/
uploads/2019/03/Resin-Impregnated-paper-bushing-construction.jpg)

 Resin Impregnated paper bushing construction

The Figure shows the cross-sectional view of RIP Bushing.

In resin impregnated paper (RIP) transformer bushing type the major insulation consists
of a core wound from paper and subsequently impregnated with epoxy resin. The casting
and curing of this insulation is a carefully controlled process.

![Resin Impregnated paper transformer bushing types](https://studyelectrical.com/
wp-content/uploads/2019/03/Resin-Impregnated-paper-transformer-bushing-types.jpg)

 Resin Impregnated paper

A resin-impregnated paper bushing can be provided with an insulating envelope (generally“
Silicone Composite insulator”), in which case the intervening space can be filled
with an insulating liquid or another insulating medium like polyurethane foam, gel,
etc.

Based on the above, it can be said that the major difference between Resin Impregnated
Paper (RIP) bushing technology and Oil Impregnated Paper (OIP) bushings is that 
in OIP technology the condenser cores are impregnated with transformer grade mineral
oil that remains in a liquid phase throughout its entire life whereas in RIP bushings
the impregnation is carried out via a curable epoxy resin to form a solid condenser.

 * OIP – condenser cores are impregnated with transformer grade mineral oil that
   remains in a liquid phase throughout its entire life.
 * RIP – impregnation is carried out via a curable epoxy resin to form a solid condenser

### Comparison Between Transformer Bushing Types [RIP vs OIP]

Now we will compare the two transformer bushing types (Oil-Impregnated vs Resin 
Impregnated Paper Bushings) based on various factors.

![Resin Impregnated paper bushing ](https://studyelectrical.com/wp-content/uploads/
2019/03/OIP-vs-RIP-transformer-bushings-comparison.jpg)

 OIP Vs RIP (comparison between transformer bushing types)

#### 1. Partial Discharge Level

Generally observed Partial Discharge level in Resin Impregnated Paper (RIP) bushings
are lower compare to Oil Impregnated Paper (OIP) bushings.

In Resin Impregnated Paper (RIP), Partial Discharge level generally observed are
less than 2 pC. However, in Oil Impregnated Paper (OIP) partial discharge is less
than 5 pC.

#### 2. Tan Delta Value

Tan delta values are low for Resin Impregnated Paper (RIP) bushings.

The Tan delta value is in the range of 0.35% or lower in the case of Resin Impregnated
Paper (RIP) bushings. But in the case of Oil Impregnated Paper (OIP) bushings, the
tan delta value is 0.45 % or lower usually.

#### 3. Insulation Class

As per [IEC standard 60137](https://www.sis.se/api/document/preview/8027083/), insulation
class of RIP bushing is Class-E (up to 120 degree C) & in OIP bushing the insulation
class is Class-A (upto 105 degree C).

#### 4. Weight & Transportation

Composite RIP bushing weight is approximately 50% of Porcelain OIP Bushing due to
this the handling, transportation & installation becomes easier in case of RIP bushings.

Also, OIP bushings are more susceptible to damage from vandalism, shipping, handling,
and installation.

#### 5. Seismic Withstand capability & Mechanical Strength

As per IEEE 693-2005, standard RIP transformer bushing type have proven very high
seismic performance level. However, OIP bushings have very low seismic performance
withstand capability.

Also, the mechanical strength of RIP transformer bushing type is very high compared
to the moderate strength of OIP transformer bushing type.

#### 6. Installation & Commissioning

Following are the advantages during the installation of RIP transformer bushing 
type over OIP bushings:-

 1. RIP bushings can be installed Vertical as well as horizontal at any angle. However,
    in the case of OIP bushings, there is a restriction during installation i.e. up
    to 30o from vertical only.
 2. Lowering of transformer oil is required during removal/installation of OIP bushing,
    the same is not required for RIP bushings.
 3. RIP bushings installation time is also very less compare to OIP bushing.

#### 7. Maintenance Aspect

Resin Impregnated Paper transformer bushing type requires fewer maintenance checks
compare to OIP transformer bushing type due to the absence of oil and porcelain.

#### 8. Flammability & Explosion Risk:

RIP transformer bushing type is made without any use of insulating oil which makes
it non-flammable.

This property also makes it a non-explosive type bushing.

However, in the case of OIP transformer bushing type, the chances of an explosion
are very high due to insulation failure/arcing. The insulation failure or arcing
can lead to huge explosion & may also be dangerous due to the outer porcelain envelop
which is brittle in nature.

### Related posts:

 [ ⌊Transformer Percentage Impedance Testing⌉How to Test Percentage Impedance of Transformer?](https://studyelectrical.com/2019/08/how-to-test-percentage-impedance-of-transformer.html)
[ ⌊Delta delta connection⌉Delta-Delta (Δ–Δ) Transformer Connection: Advantages, Working, and Application](https://studyelectrical.com/2025/07/delta-delta-%ce%b4-%ce%b4-transformer-connection-advantages-working-and-application.html)
[ ⌊Delta delta connection of transformer⌉Three-Phase Transformer Connections: Y–Y, Δ–Δ, Y–Δ, Δ–Y, V–V, T-T](https://studyelectrical.com/2025/07/three-phase-transformer-connections-y-y-%ce%b4-%ce%b4-y-%ce%b4-%ce%b4-y-v-v-t-t.html)
[ ⌊A detailed technical infographic illustrating percentage impedance in a transformer. The left side features a bold title: "PERCENTAGE IMPEDANCE OF TRANSFORMER AND ITS CALCULATION." The right side shows a 3D isometric illustration of a power transformer with cooling fins, bushings, and internal windings, labeled "Primary (HV)" and "Secondary (LV)." Above the transformer, two calculation boxes display the formulas Z% = (Vsc / Vrated) * 100 and Z = V / Isc. Below the transformer is a detailed circuit schematic for a "Transformer under test" showing a voltage source, ammeter, voltmeters, and shorted output. The background consists of a teal blueprint schematic, power line towers, and various electrical symbols. The StudyElectrical.com logo is in the bottom right corner.⌉Percentage Impedance of Transformer and Its Calculation](https://studyelectrical.com/2018/05/percentage-impedance-of-transformer-and.html)
[ ⌊Featured image for StudyElectrical.com article explaining why transformers are rated in kVA not kW. The technical illustration shows a dynamic central transformer labeled 'RATED IN kVA' glowing with electric blue and gold energy, flanked by icons representing a resistive heater load (cosφ = 1.0) and an inductive motor load (cosφ = 0.8). Swirling equations and circuit diagrams surround the unit. The StudyElectrical logo is in the bottom corner.⌉Why Transformers are Rated in kVA, Not in kW? (With Proof)](https://studyelectrical.com/2014/08/why-transformers-are-rated-in-kva-not-in-kw.html)
[ ⌊transformer-winding⌉Transformer Windings: Types and Design](https://studyelectrical.com/2022/11/transformer-windings-types-and-design.html)
[ ⌊Transformer testing at factory⌉Percentage Reactance in Power System (Transformer, Generator or Reactor)](https://studyelectrical.com/2023/01/percentage-reactance-in-power-system-transformer-generator-or-reactor.html)
[ ⌊Generator Reactors⌉Current Limiting Reactor or Series Reactor](https://studyelectrical.com/2023/09/current-limiting-reactor-series.html)
[ ⌊PD Testing Guide⌉Guide To Becoming An Expert In Partial Discharge Testing](https://studyelectrical.com/2024/01/partial-discharge-testing-guide.html)
[ ⌊Advantages and Disadvantages of Transformers⌉Advantages and Disadvantages of Transformers](https://studyelectrical.com/2025/07/advantages-and-disadvantages-of-transformers.html)