# Current Transformer (CT) – Construction and Working Principle

- Link: https://studyelectrical.com/2018/09/current-transformer-ct-construction-working-operating-principle-advantages-uses.html
- Published: 2018-09-16T07:45:00+00:00
- Author: 

A current transformer (CT) is a type of transformer that is used to measure AC current.
It produces an alternating current (AC) in its secondary which is proportional to
the AC current in its primary. Current transformers, along with voltage or potential
transformers are Instrument transformer.

Current transformers are designed to provide a scaled-down replica of the current
in the HV line and isolate the measuring instruments, meters, relays, etc., from
the high voltage
 power circuit.

The large alternating currents which can not be sensed or passed through the normal
ammeter, and current coils of [wattmeters](https://studyelectrical.com/2019/01/three-phase-power-measurement-wattmeter-method.html),
energy meters can easily be measured by use of current transformers along with normal
low range instruments.

> Related: [Working Principle of Transformer](https://studyelectrical.com/2015/04/20/working-principle-of-transformer/)

### Current Transformer Symbol / Circuit Diagram 

![Current Transformer Circuit Diagram](https://3.bp.blogspot.com/-uCpBoDIqGgQ/W51KGtYE3mI/
AAAAAAAACnc/Vj8UNBoYxLY-a9LH-aOyU3Gz-HgLCYYHwCLcBGAs/s1600/Current-Transformer.png"
Current Transformer Circuit Diagram")

Current Transformer Circuit Diagram

A **current transformer** (CT) basically has a primary coil of one or more turns
of heavy cross-sectional area. In some, the bar carrying high current may act as
a primary. This is connected in series with the line carrying high current.

![CT construction and Circuit Symbol](https://4.bp.blogspot.com/-zGs57HG7PhE/W58FQOcZnPI/
AAAAAAAACo4/wZCLCVxYqPQlN__y1NzXFztzDcghqI7hgCLcBGAs/s1600/Current%2BTransformer%
2BConstruction%2Bor%2BCircuit%2BDiagram%2Band%2BSymbol.gif "CT construction and 
Circuit Symbol")

CT construction and Circuit Symbol

![Current Transformer Circuit Symbols](https://studyelectrical.com/wp-content/uploads/
2018/09/Current-Transformer-Circuit-Symbols.jpg)

Current Transformer Circuit Symbols according to IEEE and IEC Standards

The secondary of the current transformer is made up of a large number of turns of
fine wire having a small cross-sectional area. This is usually rated for 5A. This
is connected to the coil of normal range ammeter.

Related: [Why Current Transformer (CT) Secondary Should not be Open ?](https://studyelectrical.com/2018/06/10/why-current-transformer-ct-seconday-should-not-be-open/)

## Working Principle of Current Transformer

These transformers are basically step-up transformers i.e. stepping up a voltage
from primary to secondary. Thus the current reduces from primary to secondary. 

So from the current point of view, these step down transformer, stepping down the
current value considerably from primary to secondary. 

Let,

N_(1) = Number of Primary Turns

N_(2) = Number of Secondary Turns

I_(1) = Primary Current

I_(2) = Secondary Current

For a transformer,

**I_(1)/I_(2 ) = N_(2)/N_(1)**

As N_(2) is very high compared to N_(1), the ratio I_(1) to I_(2) is also very high
for current transformers. Such a current ratio is indicated for representing the
range of the current transformer. 

For example, consider a 500:5 range then it indicates that C.T. steps down the current
from primary to secondary by a ratio 500 to 5. 

I_(1)/I_(2 ) = 500/5

Knowing this current ratio and the meter reading on the secondary, the actual high
line current flowing through the primary can be obtained. 

## Types of Current Transformer

On the basis of their applications in the field, current transformers can be broadly
classified into two types,

 1. Indoor current transformers
 2. Outdoor current transformers

### Indoor Current Transformers

Current transformers designed for mounting inside metal cubicles are known as Indoor
Current Transformers.

Depending upon the method of insulation, these can further be classified as:

 * Tape insulated
 * Cast resin (epoxy, polyurethane or polycrete)

In terms of constructional aspects, Indoor Current Transformers can be further classified
into the following types:

 1. **Bar Type CT**: The CTs having a bar of suitable size and material used as primary
    winding are known as bar-type CT s’. The bar may be of rectangular or circular 
    cross-section.
 2. **Slot/ Window/ Ring Type CT**: CTs having an opening in the center to accommodate
    a primary conductor through it is known as ‘ring-type’ (or ’slot/ window type’)
    CT.
 3. **Wound Type CT**: A CT having a primary winding of more than one full turn wound
    on the core is known as wound type CT. The connecting primary terminals may be 
    similar to those of a bar type CT or rectangular pads can be provided for this 
    purpose.

### Outdoor Current Transformer

These current transformers are designed for outdoor application. They use [transformer oil](https://studyelectrical.com/2018/05/properties-of-good-transformer-oil.html)
or any other suitable liquid for insulation and cooling. A liquid-immersed CT which
is sealed and does not communicate with the atmosphere is known as a hermetically
sealed CT.

Outdoor oil-filled CTs are further classiﬁed as

 1. live tank type CT
 2. dead tank type CT

Most of the outdoor current transformers are high voltage current transformers. 
Based on the application they are further classified into :

 1. Measurement Current Transformer
 2. Protection Current Transformer

#### Live Tank Current Transformer

In this design of instrument transformers, the tank housing the cores is kept at
the system voltage. A live tank CT is shown in the figure. It can be noted that 
the bushing of this CT is prone to damages in transit as its center of gravity is
at large height.

![Live Tank Current Transformer](https://studyelectrical.com/wp-content/uploads/
2018/09/Live-Tank-Current-Transformer.jpg)

Live Tank Current Transformer

#### Dead Tank Current Transformer

In Dead Tank design of current transformers, the tank housing the cores is kept 
at earth potential.

The figure shows a dead tank (single bushing) design which is mounting wise similar
to a live tank design but here the center of gravity is low. Hence this type of 
CT is not damaged in transit.

![Dead Tank Current Transformer](https://studyelectrical.com/wp-content/uploads/
2018/09/Dead-Tank-Current-Transformer.jpg)

Dead Tank Current Transformer

The figure depicts dead tank CT (two-bushing) which is very compact in size and 
can be mounted on a steel structure near the outdoor [circuit breakers](https://studyelectrical.com/2014/05/classification-types-of-circuit-breakers.html).

A CT having more than one core and more than one secondary winding is known as a
multi-core CT (for example, a CT having metering and protection cores).

A CT in which more than one ratio is obtainable by reconnection or tapings in primary
or secondary windings is known as a multi-ratio instrument transformer (e.g. a CT
having a ratio of 800-400-200/1 A). In such transformers, tapings in primary windings
must be avoided as far as permitted by the design.

An instrument transformer intended to serve the dual purpose of measuring and protection
is known as a dual-purpose instrument transformer.

A CT having a split metering core used for the measurement of current in a busbar
is known as a split-core CT. The spring action of a split-core CT allows the operator
to use this CT for enveloping a current-carrying low tension busbar, without stopping
the current flow.

### Measurement CT and Protection CT

A CT is similar to a power transformer to some extent since both depend on the same
fundamental mechanism of electromagnetic induction but there are considerable differences
in their design and operation.

Current Transformer used for **metering and indicating circuits** are popularly 
termed as **Measuring CT**.

Current Transformer used in conjunction with **protective devices** is termed as**
Protection CT**.

A measurement grade CT has much lower VA capacity than a protection grade CT. A 
measurement CT has to be accurate over its complete range e.g. from 5% to 125% of
normal current. In other words, its magnetizing impedance at low current levels (
and hence low flux levels) should be very high.

A metering core CT is designed to work more accurately within the rated current 
range designated. When current flow exceeds that rating, the metering core will 
become saturated, thereby limiting the amount of current level within the device.
This protects connected metering devices from overloading in the presence of fault
level current flows. It buffers the meter from experiencing excessive torques that
might be created during those faults.

![Metering CT Class](https://studyelectrical.com/wp-content/uploads/2018/09/Metering-
CT-Class.jpg)

Metering CT Class

In contrast, for a protection grade CT, the linear response is expected up to 20
times the rated current. Its performance has to be accurate in the range of normal
currents and up to fault currents. Specifically, for protection grade current transformers,
magnetizing impedance should be maintained to a large value in the range of the 
currents of the order of fault currents.

![Protection CT Class](https://studyelectrical.com/wp-content/uploads/2018/09/Protection-
CT-Class.jpg)

Protection CT Class

A protection core is designed to transform a distortion-free signal even well into
the overcurrent range. This enables the protective relays to measure the fault current
value accurately, even in very high current conditions.

For measuring CTs, the accuracy required is within the normal working range of up
to 125 percent of the rated current. For over-current conditions beyond this, accuracy
is not desired, rather there must be saturation in the core to relieve the connected
instruments of the stresses due to over-current.

Accuracy is not required for currents below the rated Value for protection CTs. 
But there must be accuracy at all higher values of current up to a maximum primary
current equal to the maximum system fault level.

The decision as to whether or not to use dual-purpose CT for measuring and protection
depends on various factors such as design, cost and space as also on the ability
of the instrument to withstand short time over-current.

### Class T and Class C Current Transformers

ANSI/IEEE standards classify CTs into two types:

 1. Class T Current Transformer
 2. Class C Current Transformer

Typically, a class T CT is a wound type CT with one or more primary turns wound 
on a core. It is associated with high leakage flux in the core. Because of this,
the only way to determine it’s performance is by test. In other words, standardized
performance curves cannot be used with these types of CTs.

For class C CT, letter designation ‘C’ indicates that the leakage flux is negligible.
Class C CTs are the more accurate bar type CTs. In such CTs, the leakage flux from
the core is kept very small. For such CTs, the performance can be evaluated from
the standard exciting curves. Also, the ratio error is maintained within ±10% for
standard operating conditions.

## Construction of Current Transformer

As we discussed above, there are three types of constructions used for the indoor
current transformers which are,

 1. Wound Type CT
 2. Toroidal (Window) Type CT
 3. Bar Type CT

**Wound Type Current Transformer** – The transformers primary winding is physically
connected in series with the conductor that carries the measured current flowing
in the circuit. The magnitude of the secondary current is dependent on the turn’s
ratio of the transformer. 

**Toroidal (Window) Type Current Transformer **– These do not contain a primary 
winding. Instead, the line that carries the current flowing in the network is threaded
through a window or hole in the toroidal transformer. Some current transformers 
have a “split core” which allows it to be opened, installed, and closed, without
disconnecting the circuit to which they are attached. 

![Wound Type CT Toroidal (Window) Type CT Bar Type CT](https://3.bp.blogspot.com/-
YG7Am1Pwg-s/W54Gf80w4II/AAAAAAAACis/7IEnFitACgYJwaOJYghazFbOYlx80g9RwCLcBGAs/s1600/
Wound-type-bar-type-window-type.png "Wound Type CT Toroidal (Window) Type CT Bar
Type CT")

Wound Type CT Toroidal (Window) Type CT Bar Type CT

**Bar-type Current Transformer** – This type of current transformer uses the actual
cable or bus-bar of the main circuit as the primary winding, which is equivalent
to a single turn. They are fully insulated from the high operating voltage of the
system and are usually bolted to the current-carrying device.

### 1. Wound Type Current Transformer

In wound type construction the primary is wound for more than one full turn on the
core.

[⌊Wound Type Current Transformer⌉⌊Wound Type Current Transformer⌉[

Wound Type Current Transformer

The construction of Wound Type Current Transformer is shown above.

In a low voltage wound type current transformer, the secondary winding is wound 
on a bakelite former. The heavy primary winding is directly wound on the top of 
the secondary winding with suitable insulation in between the two.

Otherwise, the primary is wound completely separately and then taped with suitable
insulating material and assembled with the secondary on the core.

The current transformers can be ring type or window type. Some commonly used shapes
for the stampings of window type current transformers are shown in the figure below.

The core material for wound type is nickel-iron alloy or oriented electrical steel.
Before installing the secondary winding on the core it is insulated with the help
of end collars and circumferential wraps of pressboards. Such pressboards provide
additional insulation and protection to the winding from damage due to the sharp
corners.

### 2. Bar Type Current Transformer

In this type of current transformer, the primary winding is nothing but a bar of
suitable size. The construction is shown in Figure.

![Bar Type Current Transformer](https://4.bp.blogspot.com/-O3PhvYhJEG8/W54C2hgbVQI/
AAAAAAAACoM/fK_cSPUURd4G1B17nKMbQWnHnhmBrFRhgCLcBGAs/s1600/Bar%2Btype%2Bcurrent%
2Btransformer.png "Bar Type Current Transformer")

Bar Type Current Transformer

The insulation on the bar type primary is bakelized paper tube or resin directly
molded on the bar. Such bar type primary is an integral part of the current transformer.
The core and the secondary winding are the same in bar type transformer.

The stampings used for the laminations in current transformers must have high cross-
sectional area than the ordinary transformers. Due to this, the reluctance of the
interleaved comers remains as low as possible. Hence the corresponding magnetizing
current is also small.

The windings are placed very close to each other so as to reduce the leakage reactance.
To avoid the [corona effect](https://studyelectrical.com/2015/12/corona-effect-in-power-system-transmission-lines.html),
in bar type transformer, the external diameter of the tube is kept large.

The windings are so designed that without damage, they can withstand short circuit
forces which may be caused due to a short circuit in the circuit in which the current
transformer is inserted.

For small line voltages, the tape and varnish are used for insulation. For line 
voltages above 7 kV, the oil-immersed or compound filled current transformers are
used.

![Construction of High Voltage Current Transformer](https://studyelectrical.com/
wp-content/uploads/2018/09/Construction-of-High-Voltage-Current-Transformer-.jpg)

Construction of High Voltage Outdoor Current Transformer

### Uses / Advantages of Current Transformer

Current transformers are used extensively for measuring current and monitoring the
operation of the power grid.

[⌊Application of different types of Current Transformers⌉⌊Application of different
types of Current Transformers⌉[

Application of different types of Current Transformers

Along with voltage leads, revenue-grade current transformers drive the electrical
utility’s [watt-hour meter](https://studyelectrical.com/2019/01/three-phase-power-measurement-wattmeter-method.html)
on virtually every building with three-phase service and single-phase services greater
than 200 amperes. 

High-voltage current transformers are mounted on porcelain or polymer insulators
to isolate them from the ground. 

Current transformers can be mounted on the low voltage or high voltage leads of 
a [power transformer](https://studyelectrical.com/2014/11/power-transformers-and-distribution-transformers.html).

Often, multiple CTs are installed as a “stack” for various uses. For example, protection
devices and revenue metering may use separate CTs to provide isolation between metering
and protection circuits and allows current transformers with different characteristics(
accuracy, overload performance) to be used for the devices.

### Application of High Voltage Current Transformers

Ideal for installation at metering points due to its very high accuracy.

Excellent frequency response; ideal for monitoring power quality and measuring harmonics.

Suitable for installation in AC and DC filters in converter [substations](https://studyelectrical.com/2019/04/electrical-substation-equipment-types-components-functions.html)
for [HVDC projects](https://studyelectrical.com/2018/12/what-is-hvdc-transmission-system-components.html).

**Examples of applications:**

 1. Protection for high voltage lines and substation.
 2. Protection for capacitor banks.
 3. Protection for power transformers.
 4. Revenue metering.