# Percentage Impedance of Transformer and Its Calculation

- Link: https://studyelectrical.com/2018/05/percentage-impedance-of-transformer-and.html
- Published: 2018-05-26T07:54:00+00:00
- Author: Tesla

The **percentage impedance ($\%Z$)** of a transformer is one of the most vital figures
stamped on the nameplate of every [power and distribution transformer](https://studyelectrical.com/2014/05/difference-between-power-transformer.html)
in [electrical substations](https://studyelectrical.com/2019/04/electrical-substation-equipment-types-components-functions.html).

Whether you are performing short-circuit fault calculations, sizing protective switchgear,
calculating voltage drop, or planning parallel operation, understanding $\%Z$ is
essential.

![Percentage Impedance in Nameplate of Transforemer](https://studyelectrical.com/
wp-content/uploads/2018/05/Percentage-impedance-in-the-nameplate-of-a-11kV-415-kV-
Transformer.jpeg)

Percentage Impedance in Nameplate of an 11kV/415V Transformer

In this guide, we break down what percentage impedance means, how it is measured,
step-by-step calculation formulas, real-world examples, and its exact role in power
system engineering.

## What is Percentage Impedance?

The impedance of a transformer represents the total opposition offered by its windings
to alternating current ($AC$). While impedance can technically be calculated for
each winding separately, a simple practical test allows us to measure the **equivalent
impedance** of the entire transformer without separating the primary and secondary
windings.

When engineers refer to the impedance of a transformer, they mean this **equivalent
impedance**.

## Definition of Percentage Impedance

The **percentage impedance ($\%Z$)** of a transformer is defined as the internal
voltage drop at full load due to winding resistance and [leakage reactance](https://studyelectrical.com/2023/01/percentage-reactance-in-power-system-transformer-generator-or-reactor.html),
expressed as a percentage of the rated normal voltage.

In other words: **It is the percentage of rated primary voltage required to circulate
full-load rated current through the windings when the secondary side is short-circuited.**

> 📌 **Key Concept:** If an $11\text{ kV} / 415\text{ V}$ transformer has a percentage
> impedance of $5\%$, applying just $5\%$ of $11\text{ kV}$ ($550\text{ V}$) to 
> the primary while the secondary is short-circuited will cause full-load rated 
> current to flow in both windings.

## Detailed Explanation of Percentage Impedance

If you apply full rated voltage to the primary winding while the secondary winding
is short-circuited, an extremely high current will flow. This is called the **[short-circuit current](https://studyelectrical.com/2016/03/short-circuit-causes-and-effects-application.html)(
$I_{SC}$)**, and its magnitude is dangerous because the shorted load offers almost
zero impedance.

![Percentage impedance of transformer testing](https://studyelectrical.com/wp-content/
uploads/2018/05/Percentage-impedance-of-transformer-testing.jpg)

Percentage impedance of transformer testing

#### ⚡ Quick Concept: Impedance Voltage

 * 🔴 **Full Rated Voltage** + Shorted Secondary  ⚡  _Extreme Fault Current_
 * 🟢 **Reduced Voltage (%V)** + Shorted Secondary  ⚡  _Rated Full-Load Current_

 💡 The reduced voltage percentage that produces full-load current IS the Percentage
Impedance (%Z).

To prevent damage during [transformer testing](https://www.google.com/search?q=https://studyelectrical.com/2014/08/power-transformers-testing-methods.html):

 1. The applied primary voltage is significantly reduced.
 2. As you gradually increase the primary voltage from $0\text{ V}$, the current in
    both windings increases proportionally.
 3. At a specific fraction of the rated voltage, **rated full-load current** will circulate
    through the windings.
 4. This specific fraction of the rated voltage is called the **impedance voltage**,
    and when expressed as a percentage of full primary voltage, it gives the **percentage
    impedance ($\%Z$)**.

## How to Test and Calculate Percentage Impedance

To determine equivalent impedance in a lab or manufacturing plant, a **Short-Circuit
Test** is performed:

 1. **Short Circuit the LV Side:** Either winding can be shorted, but it is standard
    and more convenient to short-circuit the low-voltage (LV) winding.
 2. **Apply Voltage on HV Side:** Just enough AC voltage is applied to the high-voltage(
    HV) winding to cause full-load current to flow in the shorted circuit.
 3. **Record Impedance Voltage ($V_{SC}$):** The applied voltage reading is recorded.

_(Want to learn more about this procedure? Read our full guide on [How to Test the Percentage Impedance of a Transformer](https://studyelectrical.com/2019/08/how-to-test-percentage-impedance-of-transformer.html).)_

## Formulas for Percentage Impedance Calculation

### 1. Percentage Impedance Formula

$$\%Z = \left( \frac{\text{Impedance Voltage}}{\text{Rated Voltage}} \right) \times
100 = \left( \frac{V_{SC}}{V_{\text{rated}}} \right) \times 100$$

### 2. Actual Impedance in Ohms ($Z$)

Using Ohm’s Law ($Z = \frac{V}{I}$), the actual physical impedance in ohms referenced
to the testing winding side is:

$$Z = \frac{V_{SC}}{I_{FL}}$$

Where:

 * $V_{SC}$ = Measured impedance voltage drop ($V$)
 * $I_{FL}$ = Full-load primary current ($A$)

> 💡 **Note on Losses:** Winding impedance consists of both resistive and reactive
> components ($Z = \sqrt{R^2 + X^2}$). Winding losses account for approximately **
> $98\%$** of this voltage drop at full load, while core/iron losses account for
> only **$1\%$ to $2\%$**. If the transformer operates at less than full load, the
> voltage drop is proportionally smaller.

![An educational infographic titled "Formulas for Percentage Impedance Calculation."
The graphic displays steps, formulas, and diagrams for calculating percentage impedance(%
Z) and actual impedance in ohms (Z). The first step shows a circuit diagram and 
the formula %Z = (Impedance Voltage / Rated Voltage) x 100. The second step includes
an illustration of a multimeter measuring a coil and details how to calculate actual
physical impedance (Z) in ohms referenced to the testing winding side using Ohm's
Law (Z = V/I). Specific equations provided are Z = Vsc / Ifl, where Vsc is measured
impedance voltage drop and Ifl is full-load primary current. A "Note on Losses" 
section uses pie charts to illustrate that winding impedance consists of both resistive
and reactive components, with winding losses accounting for approximately 98% of
the voltage drop at full load, and core/iron losses accounting for only 1% to 2%.
A final note states that if the transformer operates at less than full load, the
voltage drop is proportionally smaller.](https://studyelectrical.com/wp-content/
uploads/2018/05/Formulas-for-Percentage-Impedance-Calculation-Infographic.webp)

_Formulas for Percentage Impedance Calculation: An educational guide for students
detailing formulas, circuit diagrams, and loss distribution_.

## What is Per-Unit Impedance ($Z_{pu}$)?

In power system calculations, engineers often convert percentage impedance into **
per-unit impedance ($Z_{pu}$)**.

While percentage impedance expresses the impedance voltage drop as a percentage 
out of $100$, per-unit impedance expresses the exact same ratio as a decimal fraction
out of $1.0$.

### Relationship Formula

$$Z_{pu} = \frac{\%Z}{100}$$

$$\%Z = Z_{pu} \times 100$$

> **Example:** If a transformer has a percentage impedance of **$5\%$**, its per-
> unit impedance is **$0.05\text{ pu}$**.

### Difference Between Percentage Impedance ($\%Z$) and Per-Unit Impedance ($Z_{pu}$)

| **Feature / Property** | **Percentage Impedance (%Z)** | **Per-Unit Impedance (Zpu​)** | 
| **Base Scale** | Scaled out of **$100\%$** | Scaled out of **$1.0\text{ pu}$** | 
| **Typical Usage** | Stamped on physical **transformer nameplates** and factory test reports | Used in **power system fault calculations**, single-line diagrams, and software simulations | 
| **Why Use It?** | Easy to read and standardize during manufacturing | Prevents scaling errors when solving multi-voltage networks |

When solving complex multi-voltage power network calculations, converting all equipment
impedances to the **per-unit system** allows engineers to analyze the network as
a single continuous electrical circuit without worrying about turns ratios at every
transformer boundary.

## Step-by-Step Example Calculations of Z%

### Example 1: Calculating $\%Z$ and Impedance in Ohms

**Problem:** A $2400\text{ V} / 240\text{ V}$ transformer has a measured impedance
voltage ($V_{SC}$) of $72\text{ V}$ on the high-voltage winding, and its full-load
primary current ($I_{FL}$) is $10\text{ A}$.

 1. **Calculate $\%Z$:**$$\%Z = \left( \frac{72\text{ V}}{2400\text{ V}} \right) \times
    100 = 3\%$$
 2. **Calculate Impedance in Ohms ($Z$):**$$Z = \frac{V_{SC}}{I_{FL}} = \frac{72\text{
    V}}{10\text{ A}} = 7.2\ \Omega$$

**Interpretation:** There is a $72\text{ V}$ drop in the high-voltage winding at
full load due to winding and core impedance.

### Example 2: Calculating Maximum Symmetrical Short-Circuit Fault Level

**Problem:** Consider a $2\text{ MVA}$ transformer with a percentage impedance of
$5\%$. Calculate the maximum fault MVA available on the secondary side.

$$\text{Maximum Fault Level (MVA)} = \text{Rating (MVA)} \times \left( \frac{100}{\%
Z} \right)$$

$$\text{Maximum Fault Level} = 2\text{ MVA} \times \left( \frac{100}{5} \right) 
= 40\text{ MVA}$$

From this $40\text{ MVA}$ symmetrical fault level, protection engineers can easily
calculate the equivalent primary and secondary short-circuit fault currents.

## Factors Influencing $\%Z$ during Design

The core and winding construction creates a “natural” impedance value determined
primarily by **leakage flux**.

Leakage flux is governed by:

 * The ampere-turns of the windings.
 * The physical length and surface area of the leakage flux path.

Transformer designers intentionally vary $\%Z$ during the design phase by altering
the **volts-per-turn ratio** and adjusting the **geometric physical spacing** between
the primary and secondary windings.

## Role of Percentage Impedance in Power Systems

| **Feature / Consideration** | **High Percentage Impedance (%Z)** | **Low Percentage Impedance (%Z)** | 
| **Short-Circuit Current ($I_{SC}$)** | Lowers fault current levels | Increases short-circuit current levels | 
| **Mechanical Stress on Insulation** | Lower stress during faults | Higher electromagnetic stress on insulation | 
| **Voltage Regulation** | Higher internal voltage drop (Poorer regulation) | Lower internal voltage drop (Better regulation) | 
| **Switchgear Requirements** | Lower breaking capacity required | Heavy-duty circuit breakers needed |

### 1. Short-Circuit Fault Calculations

The short-circuit current ($I_{SC}$) that flows during a symmetrical fault is directly
calculated using $\%Z$:

$$I_{SC} = I_{\text{rated}} \times \left( \frac{100}{\%Z} \right)$$

 * Although $\%Z$ remains identical for both sides, the rated currents ($I_{\text{
   rated}}$) for the primary and secondary windings are different. Thus, the actual
   short-circuit current values in amperes will differ between primary and secondary
   sides.
 * **Trade-off:** A lower $\%Z$ improves voltage regulation (positive), but increases
   short-circuit current during a fault, producing extreme thermal and mechanical
   stress on insulation (negative). $\%Z$ must be precisely selected to balance 
   fault limits and voltage stability.

### 2. Parallel Operation of Transformers

Percentage impedance has a major role when operating transformers in parallel. For
two [transformers connected in parallel](https://studyelectrical.com/2014/10/parallel-operation-of-single-phase-transformers.html)
to share total load correctly:

$$\frac{\text{kVA}_1}{\%Z_1} = \frac{\text{kVA}_2}{\%Z_2}$$

 * If the ratio of kVA rating to percentage impedance is equal, they share load 
   proportionally.
 * If percentage impedances are unequal, the transformer with the lower $\%Z$ will
   draw a disproportionately higher share of the load, causing it to overheat and
   potentially trip.

## Permitted Manufacturing Tolerances in $\%Z$ (IEC 60076)

While a specific $\%Z$ is requested when ordering a transformer, international standards
recognize manufacturing variations.

According to **[IEC 60076](https://webstore.iec.ch/en/publication/588)**, a tolerance
of **$\pm 10\%$** on percentage impedance is permitted at the manufacturer’s end:

$$\text{Actual } \%Z = \text{Specified } \%Z \pm 10\%$$

> ⚠️ **Practical Example:** If you order a transformer with an **$8\%$** target 
> impedance, the manufactured unit’s actual nameplate impedance can legally be anywhere
> between **$7.2\%$** ($-10\%$) and **$8.8\%$** ($+10\%$).

System engineers must account for these worst-case tolerance limits when calculating
protection settings, fault levels, and busbar interrupting capabilities.

## Frequently Asked Questions (FAQs)

### Is percentage impedance the same on the primary and secondary sides?

**Yes.** Percentage impedance ($\%Z$) is a dimensionless ratio. Whether calculated
using primary voltage and primary full-load current or secondary voltage and secondary
full-load current, the resulting percentage value remains identical.

### Can percentage impedance be changed after a transformer is installed?

**No.** Percentage impedance is fixed during manufacturing based on core design,
physical winding dimensions, distance between windings, and turn count. It cannot
be altered without adding external series reactors or modifying internal windings.

### Related posts:

 [ ⌊Featured image for StudyElectrical.com article explaining why transformers are rated in kVA not kW. The technical illustration shows a dynamic central transformer labeled 'RATED IN kVA' glowing with electric blue and gold energy, flanked by icons representing a resistive heater load (cosφ = 1.0) and an inductive motor load (cosφ = 0.8). Swirling equations and circuit diagrams surround the unit. The StudyElectrical logo is in the bottom corner.⌉Why Transformers are Rated in kVA, Not in kW? (With Proof)](https://studyelectrical.com/2014/08/why-transformers-are-rated-in-kva-not-in-kw.html)
[ ⌊Transformer Bushing Types⌉Transformer Bushing Types : RIP Bushing vs OIP Bushing](https://studyelectrical.com/2019/03/transformer-bushing-types.html)
[ ⌊Transformer Percentage Impedance Testing⌉How to Test Percentage Impedance of Transformer?](https://studyelectrical.com/2019/08/how-to-test-percentage-impedance-of-transformer.html)
[ ⌊transformer-winding⌉Transformer Windings: Types and Design](https://studyelectrical.com/2022/11/transformer-windings-types-and-design.html)
[ ⌊Advantages and Disadvantages of Transformers⌉Advantages and Disadvantages of Transformers](https://studyelectrical.com/2025/07/advantages-and-disadvantages-of-transformers.html)
[ ⌊Delta delta connection⌉Delta-Delta (Δ–Δ) Transformer Connection: Advantages, Working, and Application](https://studyelectrical.com/2025/07/delta-delta-%ce%b4-%ce%b4-transformer-connection-advantages-working-and-application.html)
[ ⌊Delta delta connection of transformer⌉Three-Phase Transformer Connections: Y–Y, Δ–Δ, Y–Δ, Δ–Y, V–V, T-T](https://studyelectrical.com/2025/07/three-phase-transformer-connections-y-y-%ce%b4-%ce%b4-y-%ce%b4-%ce%b4-y-v-v-t-t.html)
[ ⌊separately excited dc generator characteristics⌉Beginner’s Guide to Separately Excited DC Generator](https://studyelectrical.com/2023/05/separately-excited-dc-generator-guide.html)
[ ⌊Generator Reactors⌉Current Limiting Reactor or Series Reactor](https://studyelectrical.com/2023/09/current-limiting-reactor-series.html)
[ ⌊DC MOTOR⌉DC Motor Problems and Solution – Step by Step](https://studyelectrical.com/2024/05/dc-motor-problems-and-solution.html)