# Insulating Materials for Power Cables

- Link: https://studyelectrical.com/2017/02/insulating-materials-for-cables-properties.html
- Published: 2017-02-04T04:29:00+00:00
- Author: 

[⌊118445775 electrical power cable wire⌉⌊118445775 electrical power cable wire⌉[

We have already discussed the [construction of underground cables](http://www.studyelectrical.com/2014/11/construction-of-underground-cables.html)
in the [previous article](http://www.studyelectrical.com/2014/11/construction-of-underground-cables.html).
In this article, we will discuss the different types of cable insulation materials
used in underground power cables.

Insulation is a non-conductive material, or a material resistant to the flow of 
electric current. It is often called a dielectric in radio frequency cables.

Insulation resists electrical leakage, prevents the wire’s current from coming into
contact with other conductors, and preserves the material integrity of the wire 
by protecting against environmental threats such as water and heat. Both the safety
and effectiveness of the wire depend on its insulation.

The satisfactory operation of a cable depends to a great extent upon the characteristics
of insulation used. Therefore, the proper choice of insulating material for cables
is of considerable importance.

### Properties Required for Insulating Materials

In general, the insulating materials used in cables should have the following properties:

 1.  a. **_High insulation resistance_** to avoid leakage current.
     b. **_High dielectric strength_** to avoid electrical breakdown of the cable.
     c. **_High mechanical strength_** to withstand the mechanical handling of cables.
     d. **_Non-hygroscopic_ **i.e., it should not absorb moisture from air or soil. The
        moisture tends to decrease the insulation resistance and hastens the breakdown
        of the cable. In case the insulating material is hygroscopic, it must be enclosed
        in a waterproof covering like the lead sheath.
     e. **_Non-inflammable_.**
     f. **_Low cost_ **so as to make the underground system a viable proposition.
     g. **_Unaffected by acids and alkalies_** to avoid any chemical action

No one insulating material possesses all the above-mentioned properties. Therefore,
the type of insulating material to be used depends upon the purpose for which the
cable is required and the quality of insulation to be aimed at. 

The principal insulating materials used in cables are rubber, vulcanized India rubber,
impregnated paper, varnished cambric, and polyvinyl chloride.

## Rubber

Rubber may be obtained from the milky sap of tropical trees or it may be produced
from oil products. It has relative permittivity varying between 2 and 3, dielectric
strength is about 30 kV/mm and resistivity of insulation is 1017 Ω cm. 

![Rubber Insulated Cable](https://3.bp.blogspot.com/-opqfwAssOiM/WJVVb861j2I/AAAAAAAAAjo/
Q6kCiPue6wQxPqG93o0r41W8udZFvkxwwCLcB/s200/rubber-insulated-cable%2BFINAL.jpg)

Rubber Insulated Cable

Although pure rubber has reasonably high insulating properties, it suffers from 
some major drawbacks viz., readily absorbs moisture, the maximum safe temperature
is low (about 38ºC), soft and liable to damage due to rough handling and ages when
exposed to light. _Therefore, pure rubber cannot be used as an insulating material._

### Vulcanized India Rubber (V.I.R.)

It is prepared by mixing pure rubber with mineral matter such as zinc oxide, red
lead etc., and 3 to 5% of sulfur. The compound so formed is rolled into thin sheets
and cut into strips.

The rubber compound is then applied to the conductor and is heated to a temperature
of about 150ºC. The whole process is called_** vulcanization**_ and the product 
obtained is known as vulcanized India rubber.

_Vulcanized India rubber has greater mechanical strength, durability and wears resistant
property than pure rubber. _

Its main drawback is that sulfur reacts very quickly with copper and for this reason,
cables using VIR insulation have a tinned copper conductor. The VIR insulation is
generally used for low and moderate voltage cables.

## Impregnated Paper

It consists of chemically pulped paper made from wood chippings and impregnated 
with some compound such as paraffinic or naphthenic material. 

[⌊Paper Insulated Cables⌉⌊Paper Insulated Cables⌉[

Paper Insulated Cables

This type of insulation has almost superseded the rubber insulation. It is because
it has the advantages of low cost, low capacitance, high [dielectric strength](https://studyelectrical.com/2018/01/difference-between-dielectric-breakdown-testing-insulation-resistance-measurement.html),
and high insulation resistance. 

The only disadvantage is that paper is hygroscopic and even if it is impregnated
with a suitable compound, it absorbs moisture and thus lowers the insulation resistance
of the cable. For this reason, paper insulated cables are always provided with some
protective covering and are never left unsealed. If it is required to be left unused
on the site during laying, its ends are temporarily covered with wax or tar. 

Since the paper insulated cables have the tendency to absorb moisture, they are 
used where the cable route has a few joints. [ Special precautions have to be taken
to preclude moisture at joints. If the number of joints is more, the installation
cost increases rapidly and prohibits the use of paper insulated cables.]

_For instance, they can be profitably used for distribution at low voltages in congested
areas where the joints are generally provided only at the terminal apparatus. _

However, for smaller installations, where the lengths are small and joints are required
at a number of places, VIR cables will be cheaper and durable than paper insulated
cables.

## Varnished Cambric

It is a cotton cloth impregnated and coated with varnish. This type of insulation
is also known as empire tape. 

[⌊varnished%2Bcambric⌉⌊varnished%2Bcambric⌉[

Varnished Cambric Insulation

 

_The cambric is lapped on to the conductor in the form of a tape and its surfaces
are coated with petroleum jelly compound to allow for the sliding of one turn over
another as the cable is bent. _

As the varnished cambric is hygroscopic, therefore, such cables are always provided
with a metallic sheath. Its dielectric strength is about 4 kV/mm and permittivity
is 2.5 to 3.8.

## Polyvinyl chloride (PVC)

This insulating material is a synthetic compound. It is obtained from the polymerization
of acetylene and is in the form of white powder. 

[⌊PVC insulated Cable⌉⌊PVC insulated Cable⌉[

PVC insulated Cable

For obtaining this material as cable insulation, it is compounded with certain materials
known as plasticizers which are liquids with high boiling point. The plasticizer
forms a gell and renders the material plastic over the desired range of temperature.

Polyvinyl chloride has high insulation resistance, good dielectric strength and 
mechanical toughness over a wide range of temperatures. 

_It is inert to oxygen and almost inert to many alkalies and acids. Therefore, this
type of insulation is preferred over VIR in extreme environmental conditions such
as in cement factory or chemical factory. _

As the mechanical properties (i.e., elasticity etc.) of PVC are not so good as those
of rubber, therefore, PVC insulated cables are generally used for low and medium
domestic lights and power installations.

It is cheap, durable and widely available. However, the chlorine in PVC (a halogen)
causes the production of thick, toxic, black smoke when burnt and can be a health
hazard in areas where low smoke and toxicity are required (e.g. confined areas such
as tunnels).

Normal operating temperatures are typically between 75ºC and 105ºC (depending on
PVC type). Temperature limit is 160ºC (<300mm2) and 140ºC (>300mm2).

## PolyEthylene (PE)

PVC and polyethylene are thermoplastic materials which means that they go soft when
heated and harden when cooled. The most common thermoplastic material is PVC. Another
one is polyethylene.

PE is part of a class of polymers called polyolefins. Polyethylene has lower dielectric
losses than PVC and is sensitive to moisture under voltage stress (i.e. for high
voltages only).

[⌊Abc Cable PE Sheath⌉⌊Abc Cable PE Sheath⌉[

PolyEthelene Insulation

This compound is used most in coaxial and low capacitance cables because of its 
exemplary electric qualities. Many times it is used in these applications because
it is affordable and can be foamed to reduce the dielectric constant to 1.50, making
it an attractive option for cables requiring high-speed transmission. 

Polyethylene can also be cross-linked to produce high resistance to cracking, cut-
through, soldering, and solvents. Polyethylene can be used in temperatures ranging
from -65°C to 80°C. 

All densities of Polyethylene are stiff, hard, and inflexible. The material is also
flammable. Additives can be used to make it flame retardant, but this will sacrifice
the dielectric constant and increase power loss.

## Thermosetting

Thermosetting compounds are polymer resins that are irreversibly cured (e.g. by 
heat in the vulcanization process) to form a plastic or rubber:

### XLPE (Cross-Linked Polyethylene)

XLPE has different polyethylene chains linked together (“cross-linking”) which helps
prevent the polymer from melting or separating at elevated temperatures. Therefore
XLPE is useful for higher temperature applications. 

[⌊450px 33KV XLPE Cable⌉⌊450px 33KV XLPE Cable⌉[

XLPE (Cross-Linked Polyethylene)

XLPE has higher dielectric losses than PE but has better aging characteristics and
resistance to water treeing. Normal operating temperatures are typically between
90ºC and 110ºC. Temperature limit is 250ºC.

### EPR (Ethylene Propylene Rubber)

EPR is a copolymer of ethylene and propylene and commonly called an “elastomer”.

[⌊3ph epr insulated cable⌉⌊3ph epr insulated cable⌉[

EPR (Ethylene Propylene Rubber)

EPR is more flexible than PE and XLPE but has higher dielectric losses than both.
Normal operating temperatures are typically between 90C and 110C. Temperature limit
is 250C.

### Related posts:

No related posts.