# Why Motor Fails? Most Common Causes

- Link: https://studyelectrical.com/2016/02/why-motor-fails-most-common-causes.html
- Published: 2016-02-22T19:04:00+00:00
- Author: 

[⌊EECO Inspire Blog Motor Failure⌉⌊EECO Inspire Blog Motor Failure⌉[
Motors are 
used everywhere in industrial environments and they are becoming increasingly complex
and technical, sometimes making it a challenge to keep them running at peak performance.

It’s important to remember that the causes of motor and drive issues are not confined
to a single domain of expertise–both mechanical and electrical issues can lead to
motor failure and being armed with the right knowledge can mean the difference between
costly downtime and improved asset uptime.

Winding insulation breakdown and bearing wear are the two most common causes of 
motor failure, but those conditions arise for many different reasons. This article
demonstrates how to detect the most common causes of winding insulation and bearing
failure in advance.

![Why%2BMotor%2BFails%2BMost%2BCommon%2BCauses](https://3.bp.blogspot.com/-qVrHhO-
L4Vg/VstISDCJSMI/AAAAAAAAByA/y7IyntRLR9U/s1600/Why%2BMotor%2BFails%2BMost%2BCommon%
2BCauses.jpg)

### Transient Voltage

Transient voltages can come from a number of sources either inside or outside of
the plant. Adjacent loads turning on or off, power factor correction capacitor banks
or even distant weather can generate transient voltages on distribution systems.
These transients, which vary in amplitude and frequency, can erode or cause insulation
breakdown in motor windings. 

Finding the source of these transients can be difficult because of the infrequency
of the occurrences and the fact that the symptoms can present themselves in different
ways. For example, a transient may appear on control cables that don’t necessarily
cause equipment damage directly, but may disrupt operations.

_Impact: Motor winding insulation breakdown leads to early motor failure and unplanned
downtime._

### Voltage Imbalance

Three-phase distribution systems often serve single-phase loads. An imbalance in
impedance or load distribution can contribute to imbalance across all three of the
phases. Potential faults may be in the cabling to the motor, the terminations at
the motor, and

potentially the windings themselves. 

This imbalance can lead to stresses in each of the phase circuits in a three-phase
power system. At the simplest level, all three phases of voltage should always have
the same magnitude.

_Impact: Imbalance creates excessive current flow in one or more phases that then
increases operating temperatures–leading to insulation breakdown._

### Harmonic Distortion

Simply stated, harmonics are any unwanted additional source of high frequency AC
voltages or currents supplying energy to the motor windings. This additional energy
is not used to turn the motor shaft but circulates in the windings and ultimately
contributes to internal energy losses. These losses dissipate in the form of heat,
which, over time, will deteriorate the insulation capability of the windings. 

Some harmonic distortion of the current is normal on any part of the system serving
electronic loads. To start investigating harmonic distortion, use a power quality
analyzer to monitor electrical current levels and temperatures at transformers to
be sure that they are not overstressed. Each harmonic has a different acceptable
level of distortion, which is defined by standards such as IEEE 519-1992.

_Impact: Decrease in motor efficiency results in added cost and an __increase in
operating temperatures._

### Reflections on drive output PWM signals

Variable frequency drives employ a pulse width modulation (PWM) technique to control
the output voltage and frequency to a motor. Reflections are generated when there
is an impedance mismatch between the source and load. Impedance mismatches can occur
as a result of improper installation, improper component selection or equipment 
degradation over time. In a motor drive circuit, the peak of the reflection could
be as high as the DC bus voltage level.

_Impact: Motor winding insulation breakdown leads to unplanned downtime._

### Sigma current

Sigma currents are essentially stray currents that circulate in a system. The sigma
currents are created as a result of the signal frequency, voltage level, capacitance
and inductance in conductors. 

These circulating currents can find their way through protective earth systems causing
nuisance tripping or in some cases excess heat in windings. Sigma current can be
found in the motor cabling and is the sum of the current of the three phases at 
any one point in time. 

In a perfect situation, the sum of the three currents would equal zero. In other
words, the return current from the drive would be equal to the current to the drive.
Sigma current can also be understood as asymmetrical signals in multiple conductors
that can capacitively couple currents into the ground conductor.

_Impact: Mysterious circuit trip due to protective earth current flow._

### Operational overloads

Motor overload occurs when a motor is under excessive load. The primary symptoms
that accompany a motor overload are excessive current draw, insufficient torque 
and overheating. 

Excessive motor heat is a major cause of motor failure. In the case of an overloaded
motor individual motor components including bearings, motor windings, and other 
components may be working fine, but the motor will continue to run hot. For this
reason, it makes sense to begin your troubleshooting by checking for motor overload.

Because 30 % of motor failures are caused by overloading, it is important to understand
how to measure for and identify motor overloading.

_Impact: Premature wear on motor electrical and mechanical components leading to
permanent failure._