# Low Voltage Circuit Breakers – Design and Construction Basics

- Link: https://studyelectrical.com/2016/01/circuit-breaker-design-and-construction-basics.html
- Published: 2016-01-24T12:23:00+00:00
- Author: 

![CIRCUIT%2BBREAKER%2BDESIGN%2BBASICS](http://3.bp.blogspot.com/-qH1FFhwEwgY/VqS61vrnn9I/
AAAAAAAABxc/c3J57Gtf890/s1600/CIRCUIT%2BBREAKER%2BDESIGN%2BBASICS.jpg)

In this article, we are going to study the basics of low voltage circuit breaker
design and construction. The [operation ](http://www.studyelectrical.com/2014/05/circuit-breaker-operating-principle-and.html)
and [arc extinction](http://www.studyelectrical.com/2014/05/principles-and-methods-of-arc.html)
of different [types of circuit breakers](http://www.studyelectrical.com/2014/05/classification-types-of-circuit-breakers.html)
were already discussed. The basic design principles of low rating circuit breakers(
[MCB](https://studyelectrical.com/2014/07/miniature-circuit-breakers-mcb-types-characteristic-curves.html),
[MCCB](https://studyelectrical.com/2015/01/moulded-case-circuit-breakers-mccb.html),
[GFCI](https://studyelectrical.com/2019/03/gfci-ground-fault-circuit-interrupter-breaker.html),
etc.) are explained here. Variations to these design principles will be discussed
later.

Circuit breakers are [electrical switchgear](https://studyelectrical.com/2015/07/what-is-switchgear-features-components-hv-mv-lv.html)
which are constructed from the following five major components. 

 1. **Frame**
 2. **Contacts**
 3. **Arc Chute Assembly**
 4. **Operating Mechanism**
 5. **Trip Unit**

The functions and features of each component are explained with pictures.

## 1. Frame

The frame provides an insulated housing to mount the circuit breaker components.
The construction material is usually a thermal set plastic, such as glass-polymer.
The construction material can be a factor in determining the interruption [rating ](http://www.studyelectrical.com/2014/06/circuit-breaker-ratings.html)
of the circuit breaker. 

Typical frame [ratings ](http://www.studyelectrical.com/2014/06/circuit-breaker-ratings.html)
include maximum voltage, maximum ampere rating, and interrupting rating.

## 2. Contacts

The current flowing in a circuit controlled by a circuit breaker flows through the
circuit breaker’s contacts. When a circuit breaker is turned off or is tripped by
a fault current, the circuit breaker interrupts the flow of current by separating
its contacts.

Contacts are of two types depending on the interrupting rating.

 * Straight-Through Contacts
 * Blow-Apart Contacts

### Straight-Through Contacts

Some circuit breakers use a straight-through contact arrangement, so-called because
the current flowing in one contact arm continues in a straight line through the 
other contact arm.

![Straight-Through Contacts Blow-Apart Contacts](http://2.bp.blogspot.com/-Xrktjx6sKKM/
VqSvdZYtb3I/AAAAAAAABwg/DV6kdCskm7w/s1600/contacts%2Bof%2Bcircuit%2Bbreaker.jpg "
Straight-Through Contacts Blow-Apart Contacts")

Straight-Through Contacts and Blow-Apart Contacts

### Blow-Apart Contacts

Blow-apart contact design is commonly used by circuit breakers with higher interrupting
ratings. With this design, the two contact arms are positioned parallel to each 
other. 

As current flows through the contact arms, magnetic fields develop around each arm.
Because the current flow in one arm is opposite in direction to the current flow
in the other arm, the two magnetic fields oppose each other. 

Under normal conditions, the magnetic fields are not strong enough to force the 
contacts apart.

![2016 01 24 16h37 45](http://4.bp.blogspot.com/-MlmmKqnkAJk/VqSxJBlTzGI/AAAAAAAABws/
M9XNW_0FNxk/s1600/2016-01-24_16h37_45.jpg)

When a fault develops, current increases rapidly causing the strength of the magnetic
fields surrounding the contacts to increase as well. The increased strength of the
opposing magnetic fields helps to open the contacts faster by forcing them apart.

 

By reducing the time required to open circuit breaker contacts when a fault occurs,
the blow-apart contact design reduces the damaging heat felt by the circuit protected
by the circuit breaker.

## 3. Arc Chute Assembly

The [arc is extinguished](http://www.studyelectrical.com/2014/05/principles-and-methods-of-arc.html)
in this assembly. The current flowing in a circuit controlled by a circuit breaker
flows through the circuit breaker’s contacts.

When a circuit breaker is turned off or is tripped by a fault current, the circuit
breaker interrupts the flow of current by separating its contacts.

This assembly is made up of several “U” shaped steel plates that surround the contacts.
As the arc developes, it is drawn into the arc chute where it is divided into smaller
arcs, which are extinguished faster.

![Arc Chute Assembly](http://4.bp.blogspot.com/-mgHQ1abCjAY/VqSx4jZ24TI/AAAAAAAABw0/
R7DnYb72FOI/s1600/2016-01-24_16h42_05.jpg "Arc Chute Assembly")

Arc Chute Assembly

Minimizing the arc is important for two reasons. 

 * First, arcing can damage the contacts. 
 * Second, the arc ionizes gases inside the molded case. 

If the arc isn’t extinguished quickly the pressure from the ionized gases can cause
the molded case to rupture._ _

_[Arcing phenomenon](http://www.studyelectrical.com/2014/05/circuit-breaker-operating-principle-and.html)
and [methods of arc extinction](http://www.studyelectrical.com/2014/05/principles-and-methods-of-arc.html)
were discussed in previous articles. _

### Operating Handle

A circuit breaker must provide a manual means for energizing and de-energizing a
circuit and must be capable of being reset after a fault condition has been cleared.

These capabilities are typically provided through the use of an operating handle.

[⌊Operating Handle⌉⌊Operating Handle⌉[

Operating Handle

 

[Molded case circuit breakers ](http://www.studyelectrical.com/2015/01/moulded-case-circuit-breakers-mccb.html)(
MCCBs) are trip free, meaning that they cannot be prevented from tripping by holding
or blocking the operating handle in the “ON” position.

 

There are three positions of the operating handle: “ON” (contacts closed), “OFF”(
contacts open), and “TRIPPED” (mechanism in tripped position, contacts open). The
circuit breaker is reset after a trip by moving the handle to the “OFF” position
and then to the “ON” position.

## 4. Operating Mechanism

The operating handle is connected to the moveable contact arm through an operating
mechanism.

In the following illustration, the operating handle is moved from the “OFF” to the“
ON” position (Figure 1). In this process, a spring begins to apply tension to the
mechanism.

When the handle is directly over the center, the tension in the spring is strong
enough to snap the contacts closed. This means that the speed of the contact closing
is independent of how fast the handle is operated.

![Operating Mechanism](http://2.bp.blogspot.com/-P2Z30XHegfc/VqS1nWGBVTI/AAAAAAAABxI/
SLf-0PBtvfQ/s1600/2016-01-24_16h51_57.jpg "Operating Mechanism of Low Rating Circuit
Breakers")

Operating Mechanism of Low Rating Circuit Breakers

The contacts are opened by moving the operating handle from the “ON” to the “OFF”
position (Figure 2). In this process, spring begins to apply tension to the mechanism.

When the handle is directly over the center, the tension in the spring is strong
enough to snap the contacts open. Therefore, contact opening speed is also independent
of how fast the handle is operated.

## 5. Trip Unit

In addition to providing a means to open and close its contacts manually, a circuit
breaker must automatically open its contacts when an overcurrent is sensed. The 
trip unit is the part of the circuit breaker that determines when the contacts will
open automatically.

![Thermal Magnetic Trip Unit](http://1.bp.blogspot.com/-jmb697NLDa4/VqS2znbT8MI/
AAAAAAAABxQ/JSFukHUcJZ0/s1600/2016-01-24_17h03_03.jpg "Thermal Magnetic Trip Unit")

Thermal Magnetic Trip Unit

 

In a thermal-magnetic circuit breaker, the trip unit includes elements designed 
to sense the heat resulting from an overload condition and the high current resulting
from a short circuit. In addition, some thermal-magnetic circuit breakers incorporate
a “Push-to-Trip” button.