# Systems of Wiring – Introduction to Electrical Wiring

- Link: https://studyelectrical.com/2015/05/systems-of-wiring-introduction-to-electricl-wiring.html
- Published: 2015-05-30T08:43:00+00:00
- Author: 

The types of internal wiring usually employed are:

 1. Cleat wiring:
 2. Wooden Casing and Capping Wiring
 3. CTS or TRS Wiring
 4. Conduit Wiring

### Cleat Wiring

In this system of internal wiring the cables used are either VIR or PVC type. The
cables are held by porcelain cleats about 6 mm above the walls or ceiling. The cleats
are made in two halves, one base and the other cap. The base is grooved to accommodate
the cables and the cap is put over it and whole of it is then screwed on wooden 
plugs (gutties) previously cemented into the wall or ceiling. Thus the cables are
firmly griped between the two halves of the cleats and secured to the supporting
wall or ceiling. 

 

The cleats used are of different sizes and different types in order to accommodate
cables of various sizes and different numbers of cables respectively. The cleats
are of three types—one groove, two grooves and three grooves to accommodate one,
two, and three cables respectively.

#### Application:

The wiring of this type is very suitable for temporary installations in dry places.
This is also acceptable where appearance is not so important and cheapness is the
main consideration. This system is not suitable for use in domestic premises.

[⌊cleat wiring wooden casing capping wiring⌉⌊cleat wiring wooden casing capping 
wiring⌉[

 

### Wooden Casing and Capping Wiring

The cable used in this type of wiring is either VIR or PVC or any other approved
insulated cables. The cables are carried through the wooden casing enclosures. The
casing consists of V-shaped grooves (usually two to hold the cables of opposite 
polarity in different groves) and is covered at the top by means of rectangular 
strip of wood, known as capping, of same width as that of casing. The capping is
screwed to the casing by means of wooden screws fixed at every 15 cm on the centre
fillet. 

 

To protect the casing against white ants first class seasoned teak wood, varnished
by shellac varnish is employed. Two or three cables of same polarity (either all
phases or all neutrals) may be run in one groove and in no case the cables of opposite
polarity should be run in the same groove. The casing is usually placed 3.2 mm apart
from the wall or ceiling by means of porcelain distance pieces of thickness not 
less than 6.5 mm in order to keep the casing dry at the back.

 

### CTS or TRS Wiring

In this type of wiring the cables used may be single core, twin core or three core
TRS cables with a circular oval shape. Usually single core cables are preferred.
TRS cables are sufficiently chemical proof, water proof, steam proof but are slightly
affected by lubricating oils. TRS aloes are run on well-seasoned, perfectly straight
and well varnished (on all four sides) teak wood batten of thickness 10 mm at least.
The width of the batten depends upon the number and size of cables to be carried
by it. 

 

The wooden battens are secured to the walls or ceiling by flat head wood screws 
to wood or other approved plugs at an interval not exceeding 75 cm. The cables are
held on the wooden batten by means of tinned brass link clips already fixed on the
batten with brass pins and spaced at an interval of 10 cm in case of horizontal 
runs and 15 cm in case of vertical runs. The wiring after erection is neatly painted
with two coats of oil-less non cracking paint as specified in IS 732 and so on.

#### Application:

The TRS wiring is suitable for low voltage installations and is extensively used
for lighting purposes everywhere i.e. in domestic, commercial or industrial buildings
except workshop where it is liable to mechanical injury. This type of wiring is 
suitable in situations where acids and alkalies are likely to be present.

[⌊CTS wiring TRS wiring Conduit wiring⌉⌊CTS wiring TRS wiring Conduit wiring⌉[

### Conduit Wiring

In this system of wiring steel tubes, known as conduits, are installed on the surface
of walls by means of saddles or pipe hooks or buried under plaster and VIR or PVC
cables are drawn into afterwards by means of a GI wire of size of about 18 SWG. 
In damp situations the conduits can be spaced from the walls by means of small wooden
blocks fixed below the pipes at regular intervals. In order to facilitate drawing
of wires numbers of inspection fittings are provided along its length. The conduits
should be electrically and mechanically continuous and connected to earth at some
suitable point. 

 

The conduits used for this purpose are of two types namely (i) light gauge (or split
type) conduit and heavy gauge (or screwed type) conduit. Light gauge or split conduit
with a seam along its length is used for cheap work. It is not water tight or even
damp proof and is not permitted on medium voltage (i.e. on voltages higher than 
250V). Screwed conduit (solid drawn or with welded seam) is used for all medium 
voltage (250 V or 600 V) circuits and in places where good mechanical protection
and absolute protection from moisture is desired. 

 

In general the finish of the conduit is black stove-enamelled, there being a smooth
coating of enamel both on the inside and outside surface of the tube. Galvanized
conduit is also employed, especially in damp situation when the conduit is on the
surface but under ordinary conditions buried in walls it offers little, if any, 
advantage over good enamelled conduits.

 