# Residual Current Protective Devices (RCCB, ELCB & RCBO)

- Link: https://studyelectrical.com/2015/05/residual-current-circuit-breakers-elcb-rccb-rcbo-working-principle.html
- Published: 2015-05-30T07:39:00+00:00
- Author: 

## What is an RCD?

A **Residual Current Device** (**RCCB, ELCB, RCBO, [GFCI](https://studyelectrical.com/2019/03/gfci-ground-fault-circuit-interrupter-breaker.html)**
etc.) is a device that is designed to provide protection against electrocution or
electrical fires by cutting off the flow of electric automatically when it senses
a ‘leakage’ of electric current from a circuit. 

Residual Current Devices have the following Specifications 

 * Sensitivity – milliAmperes (mA) 
 * Current Rating – Amperes (A)
 * Short Circuit Rating – Kilo Amperes (kA)
 * Poles – 2 Pole or 4 Pole

#### Difference between RCD, RCCB & RCBO

 Residual current protective devices are classified according to their various versions.

 * RCD is the generic term for all types of residual current protective device.
 * RCCBs are residual current operated circuit-breakers without integral overcurrent
   protection known in Germany as Fehlerstrom-Schutzschalter (FI-Schutzschalter).
 * RCBOs are devices which feature an integrated overcurrent protection unit for
   overload and short-circuit protection in addition to protection against residual
   currents.

Read [GFCI (Ground Fault Circuit Interrupter) – Working, Types, Installing and Troubleshooting](https://studyelectrical.com/2019/03/gfci-ground-fault-circuit-interrupter-breaker.html)

## Operating Principle of a Residual Current Device

The basic operating principle of a residual current device (RCCB, ELCB, RCBO etc.)
is given in the figure below.

  |  [⌊Residual%2BCurrent%2BCircuit%2BBreaker⌉](http://4.bp.blogspot.com/-wYQpotcr-8M/VWlTFE7K48I/AAAAAAAABbE/me_Qj9H2y60/s1600/Residual%2BCurrent%2BCircuit%2BBreaker.png) |  
 |  Operating principle of Residual Current Circuit Breaker |

When the load is connected to the supply through the  **Residual Current Device******(**
RCD**), the line and neutral conductors are connected through primary windings on
a toroidal transformer.

In this arrangement, the secondary winding is used as a sensing coil and is electrically
connected to a sensitive relay or solid state switching device, the operation of
which triggers the tripping mechanism. 

When the line and neutral currents are balanced, as in a healthy circuit, they produce
equal and opposite magnetic fluxes in the transformer core with the result that 
there is no current generated in the sensing coil. (For this reason, the transformer
is also known as a ‘**_core balance transformer_**‘). 

When the line and neutral currents are not balanced they create an out-of-balance
flux. This will induce a current in the secondary winding which is used to operate
the tripping mechanism. It is important to note that both the line and neutral conductors
pass through the toroid. 

[⌊rcd%2Bworking⌉⌊rcd%2Bworking⌉[

 This is how RCD protects from electrocution.

A common cause of unwanted tripping is the failure to connect the neutral through
the **RCD**, **RCDs **work equally well on single phase, three phase or three phase
and neutral circuits, but when the neutral is distributed it is essential that it
passes through the toroid. 

### Test Circuit in RCD

A test circuit is always incorporated in the **RCD**. Typically the operation of
the test

[⌊rcd⌉⌊rcd⌉[

button connects a resistive load between the line conductor on the load-side of 
the **RCD **and the supply neutral. 
  The test circuit is designed to pass current
in excess of the tripping current of the RCD to simulate an out-of-balance condition.
Operation of the test button verifies that the RCD is operational. It is important
to note, therefore, that the test circuit does not check the circuit protective 
conductor or the condition of the earth electrode.  On all RCDs a label instructs
the user to check the function of the RCD at regular intervals and to observe that
the RCD trips instantly.

### Types of Residual Current Device

There are different types of residual current devices available now. Some of them
are mentioned below.

#### 1. RCCB 

They are Residual Current Operated Circuit-Breaker without Integral Overcurrent 
Protection.

A mechanical switching device designed to make, carry and break currents under normal
service conditions and to cause the opening of the contacts when the residual current
attains a given value under specified conditions.
  It is not designed to give protection
against overloads and/or short-circuits and must always be used in conjunction with
an overcurrent protective device such as a fuse or circuit-breaker.

#### 2. RCBO 

RCBO is a Residual Current Operated Circuit-Breaker with Integral Overcurrent Protection.

A mechanical switching device designed to make, carry and break currents under normal
service conditions and to cause the opening of the contacts when the residual current
attains a given value under specified conditions.
  In addition, it is designed 
to give protection against overloads and/or short-circuits and can be used independently
of any other overcurrent protective device within its rated short-circuit capacity.

### Working of a Residual Current Device

In an **RCD**, the line and neutral conductors of a circuit pass through a sensitive
current transformer. If the line and neutral currents are equal and opposite, the
core remains balanced (Figure A). 

If there is an earth fault the neutral current will be lower than the line current.
This imbalance produces an output from the current transformer which is used to 
trip the **RCD **and so break the circuit (Figure B).

![RCD ELCB RCCB Working](https://studyelectrical.com/wp-content/uploads/2015/05/
RCD-ELCB-RCCB-Working-.jpg)

 Working Principle of Residual Current Device (RCD)

In practice, the main [Miniature Circuit Breaker](http://www.studyelectrical.com/2014/07/miniature-circuit-breakers-mcb-types-characteristic-curves.html)
[ (MCB)](http://www.studyelectrical.com/2014/07/miniature-circuit-breakers-mcb-types-characteristic-curves.html)
for the premises will probably trip, or the service fuse so the situation is unlikely
to lead to catastrophe, but it may be inconvenient. **RCDs **normally don’t offer
protection against current overloads: **RCDs **detect an imbalance between the live
and neutral currents. A current overload, however large, cannot be detected. If 
a line neutral fault occurs (a short circuit, or an overload), the **RCD **won’t
trip, and may get damaged. 

It is now possible to get an [MCB](http://www.studyelectrical.com/2014/07/miniature-circuit-breakers-mcb-types-characteristic-curves.html)
and **RCD **in a single unit called an **RCBO**. Replacing an [MCB ](http://www.studyelectrical.com/2014/07/miniature-circuit-breakers-mcb-types-characteristic-curves.html)
with an **RCBO **of the same rating is generally safe. _**RCBO **is **Residual Current
Circuit Breaker with Overcurrent Protection.**_

_Standard ratings available are 25A, 40A, 63A and 100A _

Standard Sensitivities available are 30mA. 100mA, 300mA and optionally 10mA is also
available. Electromechanical **RCCBs **are designed to operate on normal supply 
waveforms and cannot be guaranteed to operate where none standard waveforms are 
generated by loads. The most common is the half-wave rectified waveform sometimes
called pulsating dc generated by Computers, Speed control devices (VFD) and even
dimmers. 