# Construction of Underground Cables

- Link: https://studyelectrical.com/2014/11/construction-of-underground-cables.html
- Published: 2014-11-20T16:05:00+00:00
- Author: 

An underground cable essentially consists of one or more conductors covered with
suitable insulation and surrounded by a protecting cover.

Although several [types of underground cables](https://studyelectrical.com/2018/12/types-of-underground-cables.html)
are available, the type of cable to be used will depend upon the working voltage
and service requirements.

In general, an underground cable must fulfill the following necessary requirements:

 * The conductor used in cables should be tinned stranded copper or aluminium of
   high conductivity. Stranding is done so that the conductor may become flexible
   and carry more current. 
 * The conductor size should be such that the cable carries the desired load current
   without overheating and causes voltage drop within permissible limits. 
 * The cable must have a proper thickness of insulation in order to give a high 
   degree of safety and reliability at the voltage for which it is designed. 
 * The cable must be provided with suitable mechanical protection so that it may
   withstand the rough use in laying it. 
 * The materials used in the manufacture of cables should be such that there is 
   completely chemical and physical stability throughout.

## Construction of Cables

The figure shows the general construction of a three-conductor cable. The various
parts are:

 1. Cores or Conductors 
 2. Insulation 
 3. Metallic sheath
 4. Bedding 
 5. Armoring 
 6. Serving 

  |  [⌊Construction of underground cables⌉](https://2.bp.blogspot.com/-4imn1RAjHYc/XA_LKycvc3I/AAAAAAAACm8/lt1F4s7m_fcdEHUB9jtK-pBWiXKEemlTQCLcBGAs/s1600/Construction-of-underground-cables.PNG) |  
 |

Parts of an Underground Cable

  |

### Cores or Conductors

A cable may have one or more than one core (conductor) depending upon the type of
service for which it is intended. For instance, the 3-conductor cable shown in the
figure is used for 3-phase service.

The conductors are made of tinned **copper or aluminium** and are usually stranded
in order to provide flexibility to the cable. The larger the conductor, the greater
the amount of current can flow through the conductor.

The aluminium or copper conductor carries the electrical current. Aluminium conductors
are usually used for medium voltage distribution networks requiring long distances
and extensive cabling. Copper cables are used for short links in [substations](https://studyelectrical.com/2019/04/electrical-substation-equipment-types-components-functions.html)
and industrial installations where smaller cables or higher power transmitting properties
are required.

The conductor behavior is characterized by two particularly noteworthy phenomena:

 1. the [skin ](https://www.studyelectrical.com/2018/01/what-is-skin-effect-in-wires-and-cables.html)
    [effect](https://www.studyelectrical.com/2018/01/what-is-skin-effect-in-wires-and-cables.html)
    and 
 2. the proximity effect.

The [skin effect ](https://www.studyelectrical.com/2018/01/what-is-skin-effect-in-wires-and-cables.html)
is the concentration of electric current flow around the periphery of the conductors.
It increases in proportion to the cross-section of the conductor used.

 The short distance separating the phases in the same circuit generates the proximity
effect.

 In practice, the proximity effect is weaker than the [skin effect ](https://www.studyelectrical.com/2018/01/what-is-skin-effect-in-wires-and-cables.html)
and rapidly diminishes when the cables are moved away from each other.

 The proximity effect is negligible when the distance between two cables in the 
same circuit or in two adjacent circuits is at least 8 times the outside diameter
of the cable conductor.

Read: [Bundled Conductors in Transmission Lines](https://studyelectrical.com/2019/01/bundled-conductors.html)

### Insulation

Around the conductor, it is necessary to provide insulation to prevent electrical
short circuits.

Each core or conductor is provided with a suitable thickness of insulation, the 
thickness of layer depending upon the voltage to be withstood by the cable.

The insulation must be of sufficient thickness to withstand the electric field under
the rated and transient operating
 conditions. See the table on insulation thickness.

![Insulation Thickness of Underground Cable](https://studyelectrical.com/wp-content/
uploads/2014/11/Insulation-Thickness-of-Underground-Cable.png)

Insulation Thickness of Underground Cable

The commonly used materials for insulation are impregnated paper, varnished cambric,
rubber, mineral compound. 

In medium-voltage underground cables there are two main types of insulation material:

 1. **XLPE (Cross-linked Polyethylene)**
 2.  * The most common material for MV cables today.
 3. **EPR – Ethylene Propene Rubber**
 4.  * More flexible than XLPE but not as efficient at reducing losses in circuits 
       as XLPE. Cables used in marine and offshore applications are normally constructed
       with EPR insulation.

Read more on different [types of insulation materials used in underground cables](https://studyelectrical.com/2017/02/insulating-materials-for-cables-properties.html).

### Metallic sheath

In order to protect the cable from moisture, gases or other damaging liquids (acids
or alkalies) in the soil and atmosphere, a metallic sheath of lead or aluminium 
is provided over the insulation as shown in Figure. 

The main function of the metallic screen is to nullify the electric field outside
of the cable – it acts as a second electrode of the capacitor formed by the cable.
The screen needs to connect to earth at least at one point along the route.

The second function of the metallic screen is to form a radial barrier to prevent
humidity from penetrating the cable insulation system. 

When humidity and a strong electric field are present together, the insulation deteriorates
by what is called water-treeing, which can eventually cause the insulation to fail.

### Bedding

Over the metallic sheath is applied a layer of bedding which consists of fibrous
material like jute or hessian tape.

The purpose of bedding is to protect the metallic sheath against corrosion and from
mechanical injury due to armoring. 

### Armoring

Over the bedding, armoring is provided which consist of one or two layers of galvanized
steel wire or steel tape.

Its purpose is to protect the cable from mechanical injuries while laying it or 
handling it. Armoring may not be done in the case of some cables.

### Serving

In order to protect armoring from atmospheric conditions, a layer of fibrous material
like jute similar to bedding is provided over the armoring. This is known as serving.

Armoring and serving are only applied to the cables for the protection of conductor
insulation and to protect metallic sheath from mechanical injury.

## Construction Details of Single Core XLPE Insulated Armoured PVC Sheath Underground Cable

The figure shows a circular compacted stranded copper or aluminium conductor, XLPE
insulated, with copper tape screened and covered with extruded PVC bedding, aluminium
wire armored and PVC outer sheath.

![SINGLE CORE XLPE INSULATED ARMOURED PVC SHEATHED CABLE](https://studyelectrical.
com/wp-content/uploads/2014/11/SINGLE-CORE-XLPE-INSULATED-ARMOURED-PVC-SHEATHED-
CABLE.jpg)

SINGLE CORE XLPE INSULATED ARMOURED PVC SHEATHED CABLE FOR VOLTAGES 6.6 kV UP TO
AND INCLUDING 33kV

**Conductor**
 Plain circular compacted stranded copper or aluminium conductor to
IEC 60228 class 2.

**Conductor Screen**
 An extruded layer of semiconductive compound.

**Insulation**
 XLPE (cross-linked polyethylene) rated at 90 degrees C.

**Insulation Screen**

 1. Non-metallic part
     An extruded layer of semiconductive compound.
 2. Metallic part
     Copper tape screen (SCT).

**Bedding**
 The extruded layer of PVC ST2 compound.

**Armour**
 Aluminium wires shall be applied helically over the PVC bedding.

**Outer Sheath**
 PVC type ST2 to IEC 60502 color black.

_Reference: [powerandcables.com](https://www.powerandcables.com/wp-content/uploads/2016/12/Nexans-6-33kV-Medium-High-Voltage-Underground-Power-Cables.pdf)_

### Related posts: