# Parallel Operation of Single Phase Transformers

- Link: https://studyelectrical.com/2014/10/parallel-operation-of-single-phase-transformers.html
- Published: 2014-10-24T04:47:00+00:00
- Author: 

[⌊Parallel%2Boperation%2Bof%2Bsingle%2Bphase%2Btransformer⌉⌊Parallel%2Boperation%
2Bof%2Bsingle%2Bphase%2Btransformer⌉[

By parallel operation of single-phase transformers, we mean two or more transformers
are connected to the same supply bus bars on the primary side and to a common bus
bar/load on the secondary side. Such a requirement is frequently encountered in 
practice. 

Two transformers A and B connected in parallel are shown in the figure.

[⌊Untitled 3 min⌉⌊Untitled 3 min⌉[

Transformer A and B are connected in Parallel

While connecting two or more than two transformers in parallel, it is essential 
that their **terminals of similar polarities are joined to the same busbars** as
shown. 

The wrong connections may result in a dead [short-circuit](https://studyelectrical.com/2016/03/short-circuit-causes-and-effects-application.html)
and primary transformers may be damaged unless protected by [fuses](https://studyelectrical.com/2017/09/what-is-fuse-and-how-it-works.html)
or [circuit breakers](https://studyelectrical.com/2018/12/circuit-breaker-operating-principle-and.html).

### Need of Parallel Operation in Single Phase Transformers

There are **three principal reasons** for connecting transformers in parallel. 

 1. Firstly, if one transformer fails, the **continuity of supply** can be maintained
    through other transformers. 
 2. Secondly, when the load on the [substation](https://studyelectrical.com/2019/04/electrical-substation-equipment-types-components-functions.html)
    becomes **more than the capacity** of the existing transformers, another transformer
    can be added in parallel. 
 3. Thirdly, any transformer can be taken out of the circuit for **repair/routine maintenance**
    without interrupting the supply to the consumers.

Some more reasons that necessitate parallel operation of transformers are as follows.

 * Non-availability of a single large transformer to meet the total load requirement.
 * The power demand might have increased over time necessitating augmentation of
   the capacity. More transformers connected in parallel will then be pressed into
   service.
 * To ensure improved reliability. Even if one of the transformers gets into a fault
   or is taken out for maintenance/repair the load can be continued to be serviced.
 * To reduce spare capacity. If many smaller size transformers are used one machine
   can be used as spare. If only one large machine is feeding the load, a spare 
   of similar rating has to be available. The problem of spares becomes more acute
   with fewer machines in service at a location.
 * When transportation problems limit the installation of large transformers at 
   a site, it may be easier to transport smaller ones to the site and work them 
   in parallel.

## Conditions for Parallel Operation of Single Phase Transformer

In order that the transformers work satisfactorily in parallel, the following conditions
should be satisfied:

 1. Transformers should be properly connected with regard to their **polarities**.
 2. The **voltage ratings and voltage ratios** of the transformers should be the same.
 3. The **per unit or [percentage impedances](https://studyelectrical.com/2018/05/percentage-impedance-of-transformer-and.html)**
    of the transformers should be equal.
 4. The **reactance/resistance ratio**s of the transformers should be the same.

### 1. Connection with regard to Polarity

The first condition for successful parallel operation of single phase transformer
is that the transformers should be properly connected with regard to their polarities.

**This condition is absolutely essential** because wrong connections may result 
in dead short-circuit.

**Figure (i)** shows the **correct method** of connecting two single-phase transformers
in parallel.

It will be seen that around the loop formed by the secondaries, the two secondary
e.m.f.s E_(A) and E_(B) oppose and there will be no circulating current.

[⌊Transformer Connection Based on Polarity⌉⌊Transformer Connection Based on Polarity⌉[

Transformer Connection Based on Polarity (i) Correct Connections (ii) Wrong Connections

**Figure (ii)** shows the **wrong method** of connecting two single-phase transformers
in parallel. Here the two secondaries are so connected that their e.m.f.s E_(A) 
and E_(B) are additive. 

This may lead to short-circuiting conditions and a very large circulating current
will flow in the loop formed by the two secondaries.

Such a condition may damage the transformers unless they are protected by fuses 
and circuit breakers.

#### 2. Same Voltage Rating and Voltage Ratio

The next condition for parallel operation of single phase transformer is the same
voltage rating and voltage ratio.

**This condition is desirable** for the satisfactory parallel operation of transformers.

If this condition is not met, the secondary e.m.f.s will not be equal and there 
will be **circulating current** in the loop formed by the secondaries. This will
result in the unsatisfactory parallel operation of transformers.

 Let us illustrate this point. Consider two single-phase transformer A and B operating
in parallel as shown in the figure.[⌊Untitled 6 min⌉](http://2.bp.blogspot.com/-qDvHV-wXDPA/VEnGa5lw4eI/AAAAAAAABMQ/FKemldEiqps/s1600/Untitled-6-min.png)

Let Ea and Eb be their no-load secondary voltages and Za and Zb be their impedances
referred to the secondary. Then at no-load, the circulating current in the loop 
formed by the secondaries is

[⌊eqn⌉⌊eqn⌉[

Even a small difference in the induced secondary voltages can cause a large circulating
current in the secondary loop because impedances of the transformers are small. 
This secondary **circulating current** will cause current to be drawn from the supply
by the primary of each transformer.

These currents will cause copper losses in both primary and secondary. This creates
heating with no useful output.

When the load is connected to the system, this circulating current will tend to 
produce unequal loading conditions i.e., the transformers will not share the load
according to their kVA ratings. It is because the circulating current will tend 
to make the terminal voltages of the same value for both transformers.

Therefore, the transformer with a smaller voltage ratio will tend to carry more 
than its proper share of the load. 

Thus, one transformer would tend to become **overloaded** than the other and the
system could not be loaded to the summation of transformer ratings without overloading
one transformer.

Read: [Why Transformers are Rated in KVA?](https://studyelectrical.com/2014/08/why-transformers-are-rated-in-kva-not-in-kw.html)

#### 3. Equal Percentage Impedance

Another condition for parallel operation of single phase transformer is all transformers
should have equal percentage impedance.

**This condition is also desirable** for proper parallel operation of single-phase
transformers.

_If this condition is not met, the transformers will not share the load according
to their kVA ratings._

Sometimes this condition is not fulfilled by the design of the transformers.

In that case, it can be corrected by inserting proper amount of resistance or reactance
or both in series with either primary or secondary circuits of the transformers 
where the impedance is below the value required to fulfill this condition.

#### 4. Same Reactance/Resistance Ratio

If the reactance/resistance ratios of the two transformers are not equal, the [power factor](https://studyelectrical.com/2016/07/what-is-power-factor.html)
of the load supplied by the transformers will not be equal.

In other words, one transformer will be operating with a higher and the other with
a lower power factor than that of the load.

**Equal Percentage Impedance** **(Condition 3)** is much more important than **Same
Reactance/Resistance Ratio** **(condition 4)**.

Considerable deviation from **Same Reactance/Resistance Ratio** **(condition 4)**
will result in only a small reduction in the satisfactory degree of operation.

When desired, **condition (4)** also may be improved by inserting external impedance
of proper value.