# Insulation Resistance Test (IR Test) or Megger Test

- Link: https://studyelectrical.com/2014/08/insulation-resistance-test-megger-test.html
- Published: 2014-08-16T11:39:00+00:00
- Author: 

**Insulation Resistance or IR Test** is carried out by maintenance engineers to 
ensure the healthiness of the overall insulation system of electrical equipment.

It reflects the presence or absence of harmful contamination, dirt, moisture, and
gross degradation.

IR value will be usually high (several hundred Megaohms) for a dry insulation system.
Maintenance engineers use this parameter as an index of dryness of the insulation
system. 

![Insulation Resistance Tester Megger](https://studyelectrical.com/wp-content/uploads/
2014/08/Insulation-Resistance-Tester-Megger.jpg)

Insulation Resistance Tester Megger

This test is performed at or above the rated voltage to determine if there are low
resistance paths to the ground or between winding to winding as a result of winding
insulation deterioration.

The test measurement values are affected by variables such as temperature, humidity,
test voltage, and size of the transformer. 

This test should be conducted before and after repair or when maintenance is performed.
The test data should be recorded for future comparative purposes. The test values
should be normalized to 20°C for comparison purposes. 

Insulation resistance test is conducted in most of the [substation equipment](https://studyelectrical.com/2019/04/electrical-substation-equipment-types-components-functions.html)
is high and medium voltage substations.

The general rule of thumb that is used for acceptable values for safe energization
is 1 MΩ per 1000 V of applied test voltage plus 1 MΩ. Sample resistance values of
good insulation systems are shown in Table. 

#### Recommended Minimum Insulation Resistance for Transformer Winding

  |

**Rated Voltage **

**( kV)**

  |

**IR value in MΩ**

  |  
 |

**30°C**

  |

**40°C**

  |

**50°C**

  |

**60°C**

  |  
 |

66 and above

  |

600

  |

300

  |

150

  |

75

  |  
 |

33

  |

500

  |

250

  |

125

  |

65

  |  
 |

11 & 6.6

  |

400

  |

200

  |

100

  |

50

  |  
 |

Below 6.6

  |

200

  |

100

  |

50

  |

25

  |  
 |

Note: As a rough guide, the Megger values should be 2 meg. Ohms for every rating at 60°C for 11 KV and above. The Megger values double itself for every 10°C fall in temperature.

  |

## The procedure of IR Test:

The procedure of the insulation resistance test are given below

 1. First, disconnect all the line and neutral terminals of the transformer.
 2. Megger leads to be connected to LV and HV bushing studs to measure Insulation Resistance
    IR value in between the LV and HV windings. 
 3. Megger leads to be connected to HV bushing studs and transformer tank earth point
    to measure Insulation Resistance IR value in between the HV windings and earth.
 4. Megger leads to be connected to LV bushing studs and transformer tank earth point
    to measure Insulation Resistance IR value in between the LV windings and earth.

It is unnecessary to perform the insulation resistance test of transformer per phase-
wise in a three-phase transformer.

Insulation Resistance values are taken between the windings collectively as because
all the windings on the HV side are internally connected together to form either
star or delta. Also, all the windings on the LV side are internally connected together
to form either star or delta. 

Related: [Tests and Tag Courses](https://www.metrotest.co.nz/training-courses/)

###  Measurements are to be taken as follows :

 * **For Auto-transformer**
    - HV-IV to LV, 
    - HV-IV to E,
    - LV to E
 * **For Two winding transformer**
    - HV to LV,
    - HV to E,
    - LV to E
 * **For Three winding transformer**
    - HV to IV,
    - HV to LV,
    - IV to LV,
    - HV to E,
    - IV to E,
    - LV to E