# Substation Design Criteria and Studies

- Link: https://studyelectrical.com/2014/06/substation-design-criteria-and-studies.html
- Published: 2014-06-24T12:34:00+00:00
- Author: 

The most appropriate type of substation depends on such factors as voltage level,
load capacity, environmental considerations, site space limitations, and transmission
line right of way requirements. The design criteria of the substation can vary among
the system. 

![electrical substation - design criteria](https://studyelectrical.com/wp-content/
uploads/2014/06/electrical-substation-design-criteria.jpg)

With the continuing general increase in the cost of equipment, labor, land and site
treatment every effort must be made to select criteria that represent the best compromise
to satisfy system requirements at minimum cost.

The major costs are reflected in the [power transformer](https://studyelectrical.com/2014/05/difference-between-power-transformer.html),
circuit breakers disconnecting switches. The bus layout and switching arrangement
selected will determine the number of switches and power circuit breakers required.
The choice of insulation level and coordination practices affect cost considerably.

Factors must be considered in the selection of bus layout and switching arrangements
for a substation to meet system and station requirements, are

 * the substation must be reliable, economical, safe
 * simple in design as possible to provide a high level of service continuity,
 *  provision for further expansion,
 * the flexibility of operation and
 * initial and ultimate costs.

## Studies for the Design of Substation

The following studies are to be performed to establish the design criteria for a
substation. 

 1. **Load flow studies**
 2. **Short circuit studies**
 3. **Transient stability studies**
 4. **Transient overvoltage studies**

### Load flow studies

The purpose of a substation is to provide a path for reliable delivery of power 
to system loads.

Load flow studies establish the current carrying requirements of a new substation,
when all lines are in and when selected lines are out for maintenance.

After studying a number of load flow cases, the continuous and emergency ratings
required for various equipment can be determined.  The load center also can be finalized
by load flow studies. 

### Short circuit studies

In addition to the continuous current ratings, the [substation equipment](https://studyelectrical.com/2019/04/electrical-substation-equipment-types-components-functions.html)
must have short time ratings.

These must be adequate to permit the equipment to sustain, without damage the severe
thermal and mechanical stresses of short circuit currents.

In order to provide adequate interrupting capability in the breakers, strength in
post insulators and appropriate setting for protective relays, which sense the fault
current.

### Transient stability studies

Under normal conditions, the mechanical input to a generator will be equal to the
electrical output plus generator losses. So long as this continues, the [system generators](https://studyelectrical.com/2015/12/working-principle-of-alternator.html)
rotate at 50Hz.

If this balance is destroyed by upsetting the mechanical or the electrical flow,
the generator speed deviates from 50Hz and begins to oscillate about a new equilibrium
point.

The factors which affect the stability are

 * the severity of the fault,
 * the speed with which the fault is cleared and
 * ties between the machine and the system after the fault is cleared.

The aspects of transient stability that are important in substation design are

 * the type and speed, of the line and bus protection,
 * relaying,
 * the interrupting time of the breaker and
 * the bus configuration after the fault has been cleared.

### Transient overvoltage studies

Transient overvoltage may be due to lightning strokes or circuit switching. The 
most reliable means to establish switching overvoltage is through the use of a transient
network analyzer (TNA) study.

## Substation Arrangements

The [substation arrangements](https://studyelectrical.com/2019/04/electrical-substation-equipment-types-components-functions.html)
depend on physical and electrical aspects and are influenced by the following factors.

**System security**

The ideal substation is one where each circuit is controlled by a separate breaker
with facilities for replacement of bus bar or breaker in the event of a fault or
during maintenance.

System security may be specified, based on whether complete reliance on the integrity
of the substation for a percentage of outage due to periodic faults or maintenance
is permissible. 

**Operational flexibility**

For the efficient loading of the generators, it is necessary to control the MVA 
and MVAR loading under all conditions of circuit connections.

The grouping of load circuits requires to capable of being arranged giving the best
control under normal and emergency conditions.

**Simplicity of protection arrangements**

If more than one circuit is to be controlled from one CB or greater number of CBs
is to be tripped during a fault condition, the protection arrangements are complex.

The most advantageous arrangement is a single bus bar with no sectionalizing.

**Ability to limit short circuit levels**

Any arrangement which incorporates means of providing a substation into two separate
sections either completely or through reactor coupling is suitable for limiting 
short circuit levels.

**Maintenance facilities**

During the operation of the substation, maintenance will have to be carried out,
either planned or emergency. The performance of the substation during maintenance
is also dependent on the protection arrangements

**Ease of extension**

The substation arrangement shall be such that extension of bays for new feeders 
are possible as the system expands, there shall be space and expansion facilities

**Site considerations**

The availability of the site plays an important role in planning the substation.
The substations which are simple in diagram and use least number of breakers occupy
the least site.

**Economy**

A better switching arrangement on technical requirements can be constructed if the
economics are reasonable.