# Methods of Arc Extinction in Circuit Breaker

- Link: https://studyelectrical.com/2014/05/principles-and-methods-of-arc.html
- Published: 2014-05-23T16:32:00+00:00
- Author: 

The [operating principle and arc forming phenomenon](http://www.studyelectrical.com/2014/05/circuit-breaker-operating-principle-and.html)
were explained in the [previous article](http://www.studyelectrical.com/2014/05/circuit-breaker-operating-principle-and.html).
Now it is very important to extinct the arc to avoid the serious dangers. 

 

As long as this arc is sustained in between the contacts the current through the
circuit breaker will not be interrupted finally as because the arc is itself a conductive
path of electricity. For total interruption of current the circuit breaker it is
essential to quench the arc as quickly as possible. 

 

The main [designing criteria of a circuit breaker](http://www.studyelectrical.com/2016/01/circuit-breaker-design-and-construction-basics.html)
is to provide appropriate technology of arc quenching in circuit breaker to fulfill
quick and safe current interruption.  Principles and Methods of arc extinction are
discussed here. 

### Principles of Arc Extinction in Circuit Breaker

Before discussing the methods of arc extinction, it is necessary to examine the 
factors responsible for the maintenance of arc between the contacts. These are :

[⌊SF6 Circuit Breaker⌉⌊SF6 Circuit Breaker⌉[

 1. potential difference between the contacts.
 2. ionised particles between contacts

 

Taking these in turn,

When the contacts have a small separation, the p.d. between them is sufficient to
maintain the arc. One way to extinguish the arc is to separate the contacts to such
a distance that p.d. becomes inadequate to maintain the arc. 

 

However, this method is impracticable in high voltage system where a separation 
of many meters may be required.

The ionised particles between the contacts tend to maintain the arc. If the arc 
path is deionised, the arc extinction will be facilitated. This may be achieved 
by cooling the arc or by bodily removing the ionised particles from the space between
the contacts.

### Methods of Arc Extinction in Circuit Breaker

There are two methods of extinguishing the’arc in circuit breakers

 1. High resistance method
 2. Low resistance or current zero method.

#### 1. High Resistance Method

In this method, arc resistance is made to increase with time so that current is 
reduced to a value insufficient to maintain the arc. Consequently, the current is
interrupted or the arc is extinguished. 

 

The principal disadvantage of this method is that enormous energy is dissipated 
in the arc. Therefore, it is employed only in d.c. circuit breakers Land  low-capacity
a.c. circuit breakers.

 

The resistance of the arc may be increased by

 * **_Lengthening the arc –_** The resistance of the arc is directly proportional
   to its length. The length of the arc can be increased by increasing the gap between
   contacts.

 * **_Cooling the arc –_** Cooling helps in medium between the contacts. This increases
   the arc may be obtained by a gas resistance. Efficient cooling blast directed
   along the arc.

 * **_Reducing X-section of the arc –_** If the area of X-section of the arc is 
   reduced, the voltage necessary to maintain the arc is increased. In other words,
   the resistance of the arc path is increased. The cross-section of the arc can
   be reduced by letting the arc pass through a narrow opening or by having smaller
   area of contacts.

 * **Splitting the arc –** The resistance of the arc can be increased by splitting
   the arc into a number of smaller arcs in series. Each one of these arcs experiences
   the effect of lengthening and cooling. The arc may be split by introducing some
   conducting plates between the contacts.

#### 2. Low Resistance or Current zero Method

This method is employed for arc extinction in AC Circuits only. 

 

In this method, arc resistance is kept low until current zero where the arc extinguishes
naturally and is prevented from restriking inspite of the rising voltage across 
the contacts. 

 

_All modern [high power AC Circuit Breakers](http://www.studyelectrical.com/2014/05/classification-types-of-circuit-breakers.html)
employ this method for arc extinction. _

 

In an a.c. system, current drops to zero after every half-cycle. At every current
zero, the arc extinguishes for a brief moment. 

 

Now the medium between the contacts contains ions and electrons so that it has small
dielectric strength and can be easily broken down by the rising contact voltage 
known as restriking voltage. 

 

If such a break-down does occur, the arc will persist for another half-cycle. If
immediately after current zero, the dielectric strength of the medium between contacts
is built up more rapidly than the voltage across the contacts, the arc fails to 
restrike and the current will be interrupted. The rapid increase of dielectric strength
of the medium near current zero can be achieved by 

 * (a) causing the ionised particles in the space between contacts to recombine 
   into neutral molecules. 

 * (b) sweeping the ionised particles away and replacing them by unionised particles.

 Therefore, the real problem in AC arc interruption is to rapidly deionise the 
medium between contacts as soon as the current becomes zero so that the rising contact
voltage or restriking voltage cannot breakdown the space between contacts. The de-
ionisation of the medium can be achieved by :

 * (i)_ lengthening of the gap_ : The dielectric strength of the medium is proportional
   to the length of the gap between contacts. Therefore, by opening the contacts
   rapidly, higher dielectric strength of the medium can be achieved. 

 * (ii) _high pressure_. If the pressure in the vicinity of the arc, is increased,
   the density of the particles constituting the’ discharge also increases. The 
   increased density of particles causes higher rate of de-ionisation and consequently
   the dielectric strength of the medium between contacts is increased.

 * (iii) _cooling : _Natural combination of ionised particles takes place more rapidly
   if they are allowed to cool. Therefore, dielectric strength of the medium between
   the contacts can be increased by cooling the arc

 * (iv) _blast effect :_ If the ionised particles between the contacts are swept
   away and replaced by un-ionised particles, the dielectric strength of the medium
   can be increased consider-ably. This may be achieved by a gas blast directed 
   along the discharge or by forcing oil into the contact space. 

 