# Capacitor Voltage Transformer (CVT or CCVT) – Construction & Working

- Link: https://studyelectrical.com/2014/03/capacitor-voltage-transformer.html
- Published: 2014-03-24T14:07:00+00:00

**Capacitor Voltage Transformer** (CVT) or Capacitor Coupled Voltage Transformer(
CCVT) is a [switchgear](https://studyelectrical.com/2015/07/what-is-switchgear-features-components-hv-mv-lv.html)
device used to convert high transmission class voltage into easily measurable values,
which are used for metering, protection, and control of high voltage systems.

Additionally, a CVT/CCVT used as coupling capacitors for coupling high-frequency
power line carrier signals to the transmission line.

![Capacitor Voltage Transformer CVT CCVT](https://studyelectrical.com/wp-content/
uploads/2014/03/Capacitor-Voltage-Transformer-Construction-working-design-application.
jpg)

The capacitor voltage transformer (CVT) is used for line voltmeters, synchroscopes,
protective relays, tariff meter, etc. A voltage transformer VT is a transformer 
used in power systems to step down extra high voltage signals and provide a low 
voltage signal, for measurement or to operate a protective relay.

The performance of a Capacitor Voltage Transformer (CVT) or Capacitor Coupled Voltage
Transformer (CCVT) is inferior to that of the electromagnetic voltage transformer.
Its performance is affected by the supply frequency, switching transients, the magnitude
of connected burden, etc.

The capacitor voltage transformer is more economical than an electromagnetic voltage
transformer when the nominal system voltage increases above 66 kV.

The carrier current equipment can be connected via the capacitor of the Capacitor
Voltage Transformers. Thereby there is no need for separate coupling capacitors.

Capacitor Voltage Transformers also serve as coupling capacitors for coupling high-
frequency power line carrier signals to the transmission line.

CVTs in combination with wave traps are used for filtering high-frequency communication
signals from power frequency. This forms a carrier communication network throughout
the transmission network.

Capacitor type VT is used for voltages 66 kV and above. At such voltages cost of
the electromagnetic type, VT’s tends to be too high.

## Working of Capacitor Voltage Transformer (CVT/CCVT)

The [capacitors](https://studyelectrical.com/2016/12/different-types-classification-of-capacitors.html)
connected in series act like potential dividers provided the current taken by the
burden is negligible compared with the current passing through the series-connected
capacitors. 

![CVT CCVT Circuit Diagram](https://studyelectrical.com/wp-content/uploads/2014/
03/capacitive-voltage-transformer-circuit-diagram.png)

Circuit Representation of CVT or CCVT

[⌊cvt or ccvt⌉⌊cvt or ccvt⌉[

Capacitor voltage transformer section view and single line diagram

However, the burden current becomes relatively larger and ratio error and also phase
error is introduced. Compensation is carried out by ‘tuning’.

The reactor connected in series with the burden is adjusted to such a value that
at supply frequency it resonates with the sum of two capacitors. This eliminates
the error.

The construction of capacitor type VT depends on the form of a capacitor voltage
divider. Generally, high voltage capacitors are enclosed in a porcelain housing.
A large metal sheet box at the base encloses the tuning coil intermediate transformer.

In an [electrical power substation](https://studyelectrical.com/2019/04/electrical-substation-equipment-types-components-functions.html),
Capacitor Voltage Transformer in combination with Wave Trap is placed at the sending
and receiving ends of the substation. At the receiving end, they are found just 
after [lightning arrester](https://studyelectrical.com/2014/06/lightning-arrester-location-rating-and.html)
and before line isolator.

![CVT basic circuit diagram](https://studyelectrical.com/wp-content/uploads/2014/
03/Capacitor-voltage-transformer-basic-diagram.png)

Basic diagram of a Capacitor Coupled Voltage Transformer

## Construction of Capacitor Voltage Transformer (CCVT)

Capacitor Voltage Transformer consists of two primary assemblies,

 1. the high voltage capacitor sections, and
 2. the base box, housing the electromagnetic components. 

The general arrangement of a CCVT is given below,

![General Construction of CVT CCVT](https://studyelectrical.com/wp-content/uploads/
2014/03/General-Construction-of-CVT-CCVT.jpg)

General Construction of CVT CCVT

![Internal Construction of CVT](https://studyelectrical.com/wp-content/uploads/2014/
03/Construction-of-Capacitor-coupled-voltage-transformer-cvt-ccvt.png)

Internal Construction of CVT

Capacitor voltage transformer isolates the measuring instruments, meter, relays,
protections, etc., from the high voltage power circuit and provide a scaled replica
of the voltage in the HV line. Coupling Capacitors are only used for coupling high-
frequency communication signals and they are equivalent to the capacitive part of
CVT.

Series connected capacitor elements, housed in porcelain shells, each hermetically(
in an airtight manner) sealed, are referred to as capacitor sections. The dielectric
of the capacitor elements is made up of high-quality polypropylene film/paper and
impregnated with a highly processed synthetic fluid.

Each capacitor section is equipped with stainless steel below which will allow the
synthetic fluid to expand and contract with changes in ambient operating temperature
while maintaining the hermetic sealing. _It is over these capacitor sections that
most of the high voltage will be dropped.__ _

![CVT Schematic Diagram](https://studyelectrical.com/wp-content/uploads/2014/03/
Typical-schematic-diagram-of-a-capacitor-voltage-transformer.jpg)

Typical schematic diagram of a CVT

The main applications of **CVT** in High Voltage Networks ( above 36 kV ) are given
below. Tap voltage (approximately 5-12 kV depending on the type) is taken from the
lowest capacitor section and fed to an electromagnetic circuit in the cast aluminum
base box.

### Design of Capacitor Voltage Transformer

The base box contains the intermediate transformer which will provide the final 
output voltages via multiple tapped secondary windings, series compensating reactor
and Ferro-resonance control circuitry. The base box is filled with dried mineral
oil, protecting the components from environmental deterioration.

Ferro-resonance is simply and effectively controlled by the utilization of low flux
density designed magnetic circuitry and a saturable reactor controlled damping circuit
connected across the secondary winding. The Ferro-resonance suppression circuit 
does not adversely affect the transient response.

![Design of Capacitor Voltage Transformer](https://studyelectrical.com/wp-content/
uploads/2014/03/Design-of-Capacitor-voltage-transformer.jpg "Design of Capacitor
Voltage Transformer")

Design of Capacitor Voltage Transformer

**Capacitor voltage transformer** consists of a series of capacitors connected in
series on top of a tank. The electromagnetic unit is inside the tank.

The electromagnetic unit consists of an

 * [inductive transformer](https://studyelectrical.com/2015/04/working-principle-of-transformer.html)(
   5),
 * a series reactor(8) and
 * auxiliary elements.

These capacitors form a voltage divider (2, 3) between the high voltage terminal(
1) and the high-frequency terminal (4).

The capacitors, impregnated with high-grade dielectric oil, are housed in one or
more insulators. Each of them forms a hermetically sealed independent unit, with
a very stable capacitance over time.

The high-frequency terminal (4) for the PLC signal comes out of one side through
a piece of resin that separates the capacitive unit from the inductive voltage transformer.

The medium voltage inductive voltage transformer is immersed in mineral oil and 
housed inside a hermetically sealed metallic tank.

The secondary terminals are located inside a box (7) enabling connections and has
space with protection elements such as fuses or circuit breakers.

## Applications of CVT

Some of the important applications of CVT are:

 * **Voltage Measuring**: They accurately transform transmission voltages down to
   useable levels for revenue metering, protection and control purposes.
 * **Insulation**: They guarantee the insulation between the HV network and LV circuits
   ensuring safety condition to control room operators.
 * **HF Transmissions**: They can be used for Power Line Carrier (PLC) coupling.
 * **Transient Recovery Voltage**: When installing in close proximity to HV/EHV 
   Circuit Breakers, CVT’s own High Capacitance enhance C/B short line fault / TRV
   performance.

### Example of Applications

Some of the examples of the application of CVT (Capacitor Coupled Voltage Transformer)
are,

 1. **Revenue metering.**
 2. **[Protection for high voltage lines](https://studyelectrical.com/2018/02/types-of-overcurrent-relays-for-transmission-line-protection.html)
    and substations.**
 3. **Transmission of high-frequency signals.**

### Related posts: